Run Analogue Output test

To test analogue output level user can initiate the analogue output test in Test menu. Once
Analogue Output option selected press Enter Key. Screen will display the analogue output
level. User can increase or decrease the output signal level via using up and down keys.
Analog Output
02.0 mA
To return back from Analogue Output test please press Enter key till the screen updated with
previous menu items.

Run Bump Test

Bump test can be run at any time when needed. The Bump test runs depending of the
parameters defined for bump test in configuration details. To initiate bump test please select
Bump test menu item in Test menu and press Enter key. Screen will display messages that
requesting user to apply test gas and press Enter
Apply test gas
> 15%LEL
Press enter
User should provide necessary gas and press Enter. The screen will return back to
measurement screen and show the measurement for 30 seconds.
100
BUMP TEST
28
METHANE
2 %LEL
0
Apply gas
While test executed detector will automatically went in to inhibited mode and Fault LED will
start blinking. After 30 seconds screen will alert user to remove the test gas from detector:
PRS-UM-PQ-EN-Rev.05-18.06.2020