Download Print this page
Prosense PQ Series Quick Installation Manual

Prosense PQ Series Quick Installation Manual

Hide thumbs Also See for PQ Series:

Advertisement

Quick Links

Prosense PQ Series Quick Installation Guide 
Detector connections
Prosense detectors preconfigured to provide signal from analogue output depending on 
the detector and gas type:
Function  
  
  
Signal output 
  
  
Detector Main board and connection details given in Diagram‐1: 
Power LED 
Relay Module 
Connections 
Battery 
 
 
Sensor connections are input to detector main board and already connected to sensor 
inside the sensor head. Detector connections are listed in Table‐2: 
Port 
RS485‐A 
RS485‐B 
PRS‐QIG‐PQ‐EN‐Rev.01‐11.2018 
 
 
Value/Setting  
2.0 mA 
2.0 mA to 2.5 mA 
3mA 
4.0 mA to 20.0 mA  
21.0 mA  
Table 1: Detector signal level details 
Sensor Connections 
Diagram 1: Detector main board and connections 
Usage 
V + 
Power input (+) 12VDC – 24VDC 
V ‐ 
Power input (‐) 12VDC – 24VDC 
Current Output Signal (4mA – 20mA) 
Serial connection port A 
Serial connection port B 
Table 2: Detector output ports and their usage 
Meaning 
Fault 
Warm‐up 
Calibration mode 
Normal gas measurement 
Maximum over range 
RS485 termination pins 
Display module 
Connections 
V‐ 
V+ 
RS485‐B 
RS485‐A 
 

Advertisement

loading

Summary of Contents for Prosense PQ Series

  • Page 1 Prosense PQ Series Quick Installation Guide  Detector connections Prosense detectors preconfigured to provide signal from analogue output depending on  the detector and gas type:   Function   Value/Setting   Meaning     2.0 mA  Fault     2.0 mA to 2.5 mA  Warm‐up  Signal output  3mA  Calibration mode     4.0 mA to 20.0 mA   Normal gas measurement     21.0 mA   Maximum over range  Table 1: Detector signal level details  Detector Main board and connection details given in Diagram‐1:  Power LED  S  V‐  Relay Module  Connections  V+  RS485‐B  Battery  RS485‐A  RS485 termination pins  Display module  Connections     ...
  • Page 2 Prosense PQ Series Quick Installation Guide  Detector Configuration The Prosense PQ detector has 4‐20mA analogue output and RS485 Modbus serial  communication output features on main board. It is possible to install optional relay  module to have three relay outputs for two alarm levels and fault status.   4‐20 mA output: The default configuration provides single 4‐20mA signal output. Prosense detectors can be  connected to control panels on the market having 4‐20mA input signal. Signal wiring from  detector and the control panel should be carried out by shielded cables. Wires cross  section depends on the distance between the control panel and the detector. The details  given in power cabling are valid as well for signal output. Please avoid any interruption in  case any junctions on wires. The shield is to be grounded from the control panel side only  and never connect the shield to the detector. Please make sure clutching or crimping  apparatus are not loosen or oxidized.  To get the analogue output signal correctly and constant the load resistor on S output  should be between 100‐500 Ohms if the power source is greated than 15VDC (15‐24 VDC)  at detector input. If the power source is below 15VDC (12‐15 VDC) the load resistor on S  output should be between 100‐300 Ohms. If the load resistor below 100 Ohms the  detector will behave as the S output is in short circuit status and enable the automatic  output saving mode resulting with reducing signal level to 2mA.  Commissioning WARNING: The following procedure should be followed carefully and only performed by  suitably trained personnel.  The following procedure requires the detector cover to be removed while carrying out  supply voltage checks. Therefore, the appropriate permits to work should be sought in  preparation. Prior to carrying out any HOT WORK ensure local security and site procedures  are followed. Ensure that the associated control panel output actuation is inhibited so as to  prevent false alarms. Follow below steps for commissioning:  1. Remove the detector cover   2. Configure the detector's analogue output signal and power input connections correctly  3. Check that all electrical connections are terminated correctly  4. Switch On the external power supply to feed the detector  5. Using a Digital Multi Meter (DMM), check the Supply Voltage at the terminals V+ (24V)  and V‐ (0V), this should be a minimum supply voltage of 12VDC (Maximum supply ...
  • Page 3 Prosense PQ Series Quick Installation Guide  completed LCD screen will show monitoring screen with detector information and  WARMUP message on status line. The Fault LED is lit in this period.  8. Wait two minutes to complete warm‐up period. If using PQD, WARMUP message will  be removed from status line and fault LED gone off. The LED on main board will start  blinking once in a second and analogue output signal will be 4mA.   9. Switch Off the external power to the detector.  10. Fit the cover and make sure none of the cables cause an obstruction while fitting cover  11. Switch on external power to the detector.  Electrical Specifications:  Input Voltage Range  12 to 24VDC (24VDC nominal)  Max Power Consumption  Max 4 Watts. at 24VDC  Current output  4‐20mA  2.0 mA  Fault  2.0 mA to 2.5 mA  Inhibit (during configuration/warming)  3mA  Calibration mode  4.0 mA to 20.0 mA  Normal gas measurement  21.0 mA  Maximum over range  Terminals  3 x screw terminals suitable for wire diameter 0.5 mm² to 2.5 mm²  (20AWG to 13AWG).  2 x screw terminals suitable for wire diameter 0.5 mm² to 2.5 mm²  (20AWG to 13AWG) for RS485 digital output  Relays  3 x (1A 30VDC, 0.5A 125VAC, 0.3A 80VDC). Selectable normally open or  normally closed (switch) and de‐energized.  Communication  RS485, Modbus RTU ...
  • Page 4 Prosense PQ Series Quick Installation Guide  SAFETY INSTRUCTIONS FOR HAZARDOUS AREA INSTALLATION Prosense PQ series gas detectors are projected and built according to ATEX Directive 2014/34/EU with  reference to standard EN 60079‐0, EN 60079‐1. “ATEX“, by the French "ATmosphere EXplosible”, provides the  technical requirements to be applied to equipment intended for use in potentially explosive atmospheres. The  scope of directive is to remove technical barriers to trade between Member States of the European  Community. The Prosense PQ series gas detectors must be installed and maintenance according to the suitable  standards for electrical application in potentially explosive atmospheres (example: EN 60079‐14, EN 60079‐17  or other national standards). Read this instruction first and keep this instruction manual always available.  The following instructions apply to equipment covered by ATEX certificate number:   1. Prosense PQ series gas detectors may be installed in hazardous area with flammable gases, vapours, and  mist, group II, category 2G, maximum superficial permissible temperature 70°C.  Device category 2G, Identification II 2G  Ex db IIC T6 Gb (Tamb = ‐20°C : +70°C)  It means:   (European Community logo for ATEX applications) – group II (potentially explosive atmospheres  – surface application – OTHER than mines)    Category 2G ( G => Gas ) – Zone 1 and Zone 2    Ex db => protection mode: explosion proof enclosure    IIC => define kind of gases    T6  => Temperature class ‐‐ Maximum allowable surface temperature.    IP 65 => Mechanical protection degree – protection against solid, dust and liquid.  2. Suitably trained personnel shall carry out installation in accordance with applicable code practice.  3. The electrical devices must be grounded using their grounding connections. The grounding connection must  be ATEX certified, suitable for the application required, substances, maximum superficial temperature, and  ambient temperature.  4. The user should guarantee periodical cleaning of the places were dust can storage to avoid the paling up to 5  mm.  5. The user should not repair this equipment.  6. The user should guarantee the keeping of the safety characteristic of the device after maintenance of ...