Mounting the detector

The detector should be mounted vertically as the sensor head pointing downwards. Detector
has to be mounted such that the sensor's gas entrance area. The install location
• should be isolated from vibration, direct sun light and have temperature stability
• avoided external influences such as splashing water, oil, corrosive aerosols
• should have at least 30 cm free space beneath the sensor head to provide
accessibility for calibration work.
• should be in air flow between possible leak or collection point and possible source of
ignition.
Prosense do not recommend installing detectors to:
• directly above a cooking unit,
• directly above a sink unit,
• close to an extractor unit,
• outdoor without protection against the rain,
• in places where temperature is outside the admissible operating range,
• corrosive environments,
• inside air vents.
• environments where silicon can be found.
Prosense PQ series detector has mounting two mounting holes on detector body to fix
detector directly to a surface:
Mounting hole
PRS-UM-PQ-EN-Rev.05-18.06.2020
Diagram 6: Mounting holes
Mounting hole
14