If user finish the work or test it is necessary to clear inhibit mode to return detector to normal
operation. To do this user should re-enter to Inhibit menu in Test menu. The clear option will
be displayed at this time:
Run Display test
To execute display tests select Display option on Test menu and press Enter key. The detector
program will start display test via drawing different patterns. It might take one minute to
complete test. The display will return back to Test menu when test completed.
Run Relay test
It is possible to check relay functions via using menu options. Relays are only available if
optional relay module installed on to detector main board. To run relay test please select test
menu and select Relay option. Screen will display three options to test as there are three
relays on relay module. Select the menu option related to desired relay test and press Enter
key.
If fault relay test selected, detector will activate the relay and screen will display information:
If alarm relay selected, detector will activate related alarm relay and screen will display
information:
PRS-UM-PQ-EN-Rev.05-18.06.2020
1. Clear
2. Previous Menu
1. Fault Relay
2. Alarm 1 Relay
3. Alarm 2 Relay
4. Previous Menu
Fault Relay
is active
Alarm 1 Relay
is active