The first digit on screen will start blinking once entered the menu step. You can increase or
decrease the value via using up and down keys. Once desired value has been set press Enter
key to confirm and move to the next digit to set. Once all set press Enter key. The display will
show "Successful" message and return back to higher level menu.
Change Modbus address
To change detector address, select "Modbus Address" menu option. In RS485 communication
detectors are slave devices and control panel is the master device. Each detector must have
unique address to work together in same RS485 communication loop. Select "Modbus
Address" menu item via using up and down keys and press Enter key. Display will show default
detector address which is 1:
Address can be changed with up and down keys. Once set to desired address press Enter key
long enough. The display will show "Successful" message and return back to higher level
menu.
Change Analogue Output
User can adjust analogue output levels depending of the status and function. To do this please
select "Analogue Output" menu item on configuration menu via using up and down keys and
select Enter key. Screen will display default values used for analogue output:
Display Parameters
User can adjust these values to desired values depending of the application requirements.
Detector display can be adjusted as per requirements. The display options are given in Display
menu item
PRS-UM-PQ-EN-Rev.05-18.06.2020
Modbus Address
1
4-20mA Output
Fault
Warm Up
Calibration
Inhibit
Over Range
1. Language
2. Zero Suppression
3. Password
4. Detector model
5. Previous Menu
: 2.0 mA
: 3.0 mA
: 3.0 mA
: 3.0 mA
: 22.0 mA
30