3.1
General
The EE160 probe is optimized for cost effective, accurate measurement of relative humidity (RH) and
temperature (T) in building automation.
The measured data is available on
two voltage or current (2-wire) outputs
the RS485 interface with BACnet MS/TP or Modbus RTU protocol
a passive T output
Both, the wall mount and the duct mount model come with an IP65 / NEMA 4 enclosure which
provides minimal installation costs and reliable protection against contamination and condensation.
The encapsulated electronics and the E+E sensor coating ensure long-term stable and accurate
measurements.
The user can set the RS485 interface parameters, the output scaling and perform one or two point
adjustment for RH and T with an optional configuration adapter and the free EE-PCS Product
Configuration Software.
3.2
Dimensions
5
0.2"
Recommended mounting screws:
ST4.2x50 DIN7981C
Fig. 1
Dimensions of EE160 in mm and inch
3.3
Electrical Connection
EE160-M1TxJ3
DO NOT CONNECT!
6
CABLE GLAND
Ø > 16
Ø > 0.63"
M16x1.5
Ø 12
Ø 0.47"
Connector for configuration adapter
Bus termination resistor 120 Ω (jumper)
User Manual EE160 Humidity and Temperature Sensor for HVAC Applications
Ø > 13
Ø > 0.51"
-
Output:
Ø 12
0 - 10 V
Ø 0.47"
GASKET
60
±0.3
2.36
"
±0.11
6
0.24"
-
-
Output:
4 - 20 mA
-
Output:
Modbus RTU or
BACnet MS/TP
5
0.2"
19
0.75"
CABLE GLAND
M16x1.5