RH / T Adjustment and Calibration
Definitions
Calibration documents the accuracy of a measurement device. The device under test (specimen) is
compared with the reference and the deviations are documented in a calibration certificate. During
the calibration, the specimen is not changed or improved in any way.
Adjustment improves the measurement accuracy of a device. The specimen is compared with the
reference and brought in line with it. An adjustment can be followed by a calibration which documents
the accuracy of the adjusted specimen.
Depending on the application and the requirements of certain industries, there might arise the need for
periodical humidity calibration (comparison with a reference) or adjustment (bringing the device in line
with a reference).
Calibration and adjustment at E+E Elektronik
Calibration and/or adjustment can be performed in the E+E Elektronik calibration laboratory. For
information on the E+E capabilities in ISO or accredited calibration please see www.eplusecal.com.
Calibration and adjustment by the user
Depending on the level of accuracy required, the humidity reference can be:
• Humor 20 Humidity Calibrator, please see www.epluse.com.
• Omniport30 handheld device, please see www.epluse.com/omniport30.
• Certified salt solutions, please see www.epluse.com/EE160.
Cleaning of the sensing head:
Use in polluted environment might rise the need for cleaning the sensing head and replacing the filter
cap. In such a case please see "Cleaning Instructions" at www.epluse.com/EE160.
When employed in dusty, polluted environment:
The filter cap shall be replaced once in a while with an E+E original one. A polluted filter cap causes
longer response time of the device.
If needed, the sensing head can be cleaned. For cleaning instructions please see
EE160.
While replacing the filter cap take very good care to not touch or rub the sensing element.
6
Accessories
Please also refer to the "Accessories" data sheet.
Description
E+E Product Configuration Software
Power supply adapter
Protection cap for 12 mm probe
USB configuration adapter for EE160-M1TxJ3 (RS485)
Product configuration adapter for EE160-MxTxAx (analogue output)
User Manual EE160 Humidity and Temperature Sensor for HVAC Applications
(Download: www.epluse.com/configurator)
www.epluse.com/
Order code
EE-PCS
V03
HA010783
HA011066
see datasheet EE-PCA