Recloser Accessories; Terminal Options; Mounting Hangers - Eaton COOPER POWER Series M Installation And Operation Instructions

Single-phase recloser system
Table of Contents

Advertisement

Figure 28 . Side-panel serial RS-232 communication port
option
Table 14 . Communication support equipment
Description
USB cable, Type A male-to-Type B male connectors,
2 meters (6.5 ft.) length
Figure 29 . USB cable
J2 DB-9 Connector
1
2
6
RS-232 DTE
Figure 30 .
RS-232 serial communication port pin
identification
Table 15 . Serial communication port pin assignments
Pin number
Signal name
1 DCD
Carrier Detect
2 RXD
Receive Data
3 TXD
Transmit Data
4 DTR
Data Terminal Ready
5 GND
Signal Ground
6 DSR
Data Set Ready (Not Connected)
7 RTS
Request to Send
8 CTS
Clear to Send
9 NC
Not Used
10 (Shroud)
Chassis Ground
Catalog number
KSPRC-66
3
4
5
7
8
9
INSTALLATION AND OPERATION INSTRUCTIONS MN280048EN June 2016
SPEAR™ Single-Phase Recloser System

Recloser accessories

Terminal options

SPEAR single-phase reclosers can be specified with eyebolt
terminals (400 A , 630 A, and 800 A), two-hole (400 A,
630 A) or four-hole (800 A) flat-pad terminals, or stud-type
terminals (400 A, 630 A, and 800 A).
The eyebolt, flat-pad, and stud terminals are made of
copper alloys. Eaton recommends terminal connection
to copper wires to optimize the electrical connection.
Aluminum cables may produce aluminum oxide sufficient to
compromise the electrical connections.
Anti-oxide coatings for temporary protection of wire-
brushed, aluminum cable connections to flat-pad or stud
terminals must be maintained at intervals determined by
the customer based on load current, climate, and other
installation conditions.
Copper conductors only are recommended for eyebolt
terminals.

Mounting hangers

Crossarm mounting hanger
A crossarm mounting hanger is available for crossarm
installation. These are available in sets of two; one set is
needed for each SPEAR single-phase recloser. To order this
accessory, specify part number KA39H2.
Pole-mounting accessory
The 15 kV and 27 kV SPEAR single-phase reclosers can
be directly mounted to the pole using the built-in tank
mounting channels for BIL rating of 125 kV and lower. Due
to electrical clearances, the pole-mounting hanger accessory
is recommended for mounting either the 27kV (with 150 kV
BIL accessory), or 38 kV (170 kV BIL) SPEAR single-phase
recloser to the pole. To order this accessory, specify part
number KSPR-364.
Figure 31 .
Pole-mounting hanger views
6.6 in
(168 mm)
0.81 in
18.0 in
(457 mm)
31