SPEAR™ Single-Phase Recloser System
PHASE FAULT
ABOVE MIN TRIP
PHASE FAULT
ABOVE MIN TRIP
LOCKOUT
OPEN
CLOSED
LOCKOUT
Figure 4 .
SPEAR single-phase recloser control status
OPEN
indicator LED (left side)
TRIP
CLOSE
CLOSED
OPEN: This LED illuminates to indicate the recloser is in the
open position.
TRIP
CLOSED: This LED illuminates to indicate the recloser is in
the closed position.
(LOCKOUT)
N
otee:
There are several conditions that will cause the
alternate blinking of the control LOCKOUT, recloser
OPEN, and recloser CLOSED LEDs: Failure to Trip,
Failure to Close, Interrupter Malfunction, and 52a/b
Disagreement.
(LOCKOUT)
The LED blinking pattern for these conditions is the
control LOCKOUT LED and recloser CLOSED LED
alternating with the recloser OPEN LED.
N
otee:
Reset Targets (under Counters menu) will clear the
Interrupter Malfunction diagnostic. The alarm LED
will remain illuminated as long as the alarm condition
exists.
IMPORTANT
The CLOSED LED will blink and a countdown-to-close timer
will appear on the LCD display when a delayed CLOSE is
active. A CLOSE will occur when the manual close delay
timer expires.
6
INSTALLATION AND OPERATION INSTRUCTIONS MN280048EN June 2016
SPEAR Single-Phase Recloser Control
→*SETTINGS
*SEQUENCE OF
SPEAR Single-Phase Recloser Control
EVENTS
→*SETTINGS
*METERING
*SEQUENCE OF
EVENTS
*METERING
ENTER
ENTER
ESC
EDIT
ESC
HOT LINE
TAG
ON
HOT LINE
OFF
CLOSE
TAG
ON
OFF
This information is indicated on the right side of the control:
(Figure 5):
ALARM
CONTROL OK
ALARM
AC POWER
CONTROL OK
BATTERY
AC POWER
BATTERY
Figure 5 .
SPEAR single-phase recloser control status
indicator LED (right side)
ALARM: This LED illuminates to indicate an alarm condition
exists. The LED will flash for unacknowledged alarms, and
will continuously illuminate for acknowledged alarms that
DATA PORT
are still active. Refer to Service Information MN280012EN
SPEAR Single-Phase Recloser Control Programming Guide
for alarm list.
EDIT
DATA PORT
These Status Alarms are enabled by default:
SUPER-
NON
AC Power present
VISORY
RECLOSE
OFF
Battery Disconnect
Battery Failure
SUPER-
NON
VISORY
BATTERY
ALT
Battery Trouble
RECLOSE
OFF
TEST
PROFILE
Clock Not Set
Control Circuit Interrupted
BATTERY
ALT
Interrupter Malfunction
TEST
PROFILE
Recloser Closed: Failed to Trip
Recloser Open: Failed to Close
State Indeterminate Open and Closed
To enable or disable specific alarms, use the ProView NXG
software to configure the alarms. Refer to Section 5e:
Alarms in Service Information MN280012EN SPEAR Single-
Phase Recloser Control Programming Guide. If alarms are
not configured, the ALARM LED will not illuminate.
Loss of protection . Reconfigure the user settings .
When the CONTROL OK LED is flashing, control
protection is disabled . User protection profile settings
must be reconfigured to enable protection . Loss of
protection can result in personal injury and equipment
damage .
IMPORTANT
CAUTION
T360 .1