Mtl7700 Range - Accessories - Eaton MTL7700 Instruction Manual

Crouse-hinds series, shunt-diode safety barriers
Table of Contents

Advertisement

Type
Application
Analogue
Resistance temperature detectors
input
Thermocouples, ac sensors
(low-level)
Analogue
Controller outputs, one line earthed
output
Controller outputs, neither line earthed
Analogue
Transmitters, 2-wire, 4–20mA
input
(high-level)
Digital (on/
Switches
off) input
Digital (on/
Solenoids, alarms, LEDs
off) output
Table 1: MTL7700 range of key barriers
2 .3
MTL7700 range – accessories
MTL7700 range of barriers mount directly onto DIN-rail. A
comprehensive selection of mounting, tagging, power and earthing
accessories is available. Installation details are given in section 4.3.
Essential accessories
The following are usually considered essential for mounting and
earthing MTL7700 range of barriers:
DIN-rail (eg, THR2 or THR7000)
Insulating spacers (eg, ISP7000)
Earth terminal (eg, ETL7000)
TAG57
Figure 2: MTL7700 range of mounting and tagging accessories
INM 7700 Rev 12
The tagging systems for individual modules and columns of
Key barriers
barriers are described here. They are shown below under Tagging
accessories for columns of barriers.
7755ac
Mounting accessories (figure 2)
7756ac
7760ac
THR2
7728+
THR7000
7787+
dc power supply
ISP7000
26V
20-35V
7787+
7706
Tagging accessories for individual barriers (figure 2)
TH7700
7787+
7707+
Tagging accessories for columns of barriers (figure 2)
7741-44
TAG57
7728+
7707+
TGL7700
IMB57
Power accessories (figure 3)
BPL7700
Earthing accessories (figure 3)
ETL7000
ERB57S
TGL7700
2
Standard DIN-rail, 35 x 7 .5mm, (in 1m lengths)
Nickel-plated DIN-rail, 35 x 7 .5mm, for use in
potentially corrosive atmospheres (in 1m
lengths)
Insulating spacer: attaches to the base of a DIN-
rail to isolate the IS earth from a structural earth
Tag holder for mounting on the top of an
individual barrier
Tagging strips for mounting over a column of
barriers, for marking barrier locations. Supplied
(with labels) in 1m lengths for cutting to size.
Spare labels for use with TAG57 tagging strips:
0.5m strips, supplied in sets of 10.
Tagging strip supports. Two needed for each
tagging strip. It can also be used as centre
support by breaking off the top end tab.
Power link for feeding 24V dc to a maximum of
40 barriers in a single column from an MTL7798
power feed module or MTL7799 Dummy
module.
Earth terminal providing connections for
routeing the IS earth from the DIN-rail to an
appropriate plant earth. Two recommended for
each length of DIN-rail.
Nickel-plated straight earth-rail bracket, supplied
with two push fasteners, one 14mm earth-rail
clamp and one 9mm earth clamp < 16mm
TH7700
ERB57O
IMB57
ETL7000
ISP7000
2
.

Hide quick links:

Advertisement

Table of Contents
loading