CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other- wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or...
FOR LIFE FOR LIFE Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power™ series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service.
Unpack the Introduction PUSH-OP connector and inspect it thoroughly for damage Eaton's Cooper Power™ series 600 A, 15, 25, and 35 kV incurred during shipment. If damage is discovered, file a Class PUSH-OP™ deadbreak connector offers a complete claim with the carrier immediately.
Refer to Figure 5. Test for voltage by fuzzing or by using voltage detector • designed for connectors. Remove probe after testing. figure 6. Provide a visible ground with a grounding elbow. 600 A PUSH-oP DeADbreAk connector oPerAtion inStrUctionS MN650011EN May 2017...
Page 8
Ensure that PUSH-OP bail bracket on the insulated standoff bushing is unlatched. Refer to Figure 7 . figure 8. unthread the hitch pin. figure 7. Mount PuSH-oP standoff bushing. 600 A PUSH-oP DeADbreAk connector oPerAtion inStrUctionS MN650011EN May 2017...
Page 9
Thread hitch pin clockwise until bail lock is secured. remove the grounding elbow from the 200 A interface • during this operation. Refer to Figure 10. figure 10. Move PuSH-oP connector to insulated bushing. 600 A PUSH-oP DeADbreAk connector oPerAtion inStrUctionS MN650011EN May 2017...
Page 10
Refer to Figure 13. figure 14. Pull on push plate to ensure latch plate is engaged. figure 13. install adapter on PuSH-oP apparatus bushing. 600 A PUSH-oP DeADbreAk connector oPerAtion inStrUctionS MN650011EN May 2017...
Remove bushing adapter by unhooking catch strap ring. Place bushing adapter in clean protected area. Refer to Figure 18. figure 16. Engage catch strap in push plate slots. 600 A PUSH-oP DeADbreAk connector oPerAtion inStrUctionS MN650011EN May 2017...
Page 12
Refer to Figure 19. figure 19. Pull back until connector is unsealed. figure 21. Pull on push plate to ensure latch plate is engaged. 600 A PUSH-oP DeADbreAk connector oPerAtion inStrUctionS MN650011EN May 2017...
Page 13
22. Place cap on 200 a connector interface. Repeat Steps 1 and 2 for all three phases on both ends of cable. Remove all tool, test equipment and personal protective equipment from work area before energizing apparatus. 600 A PUSH-oP DeADbreAk connector oPerAtion inStrUctionS MN650011EN May 2017...
Page 14
This page intentionally left blank. 600 A PUSH-oP DeADbreAk connector oPerAtion inStrUctionS MN650011EN May 2017...
Page 15
This page intentionally left blank. 600 A PUSH-oP DeADbreAk connector oPerAtion inStrUctionS MN650011EN May 2017...