Programming panel
CAUTION
Equipment misoperation . Use of the control front
panel HMI may result in several combinations of
settings, configurations, and customizations . The user
must ensure that a proper combination is created and
downloaded for the appropriate device application .
The Programming panel has the following sections:
LCD display (Figure 3)
The LCD display is a 4-line, 16-character display.
The keypad functionality is summarized as follows.
The
(up) key can be used for the following tasks:
●
●
Scroll to the next item up on the current Menu level
●
●
If already at the first item of the current Menu level,
●
●
return to the last item of the current Menu
When editing a selectable option parameter, scroll up
●
●
to the next available option
Decrement the value of a digit (example: from 6 to 5)
●
●
SPEAR Single-Phase Recloser Control
→*SETTINGS
*SEQUENCE OF
EVENTS
*METERING
ENTER
ESC
EDIT
Figure 3 .
LCD display and keypad functionality
HOT LINE
The
(down) key can be used to complete the following
CLOSE
●
●
TAG
tasks:
Scroll to the next item down on current Menu level
●
●
ON
If scrolled past the last line of the current Menu level,
OFF
●
●
return to the first line of the current Menu
When editing a Selectable Option Parameter, scroll
●
●
down to the next available option
Increment the value of a digit (example: from 3 to 4)
●
●
ALARM
CONTROL OK
AC POWER
BATTERY
DATA PORT
SUPER-
NON
VISORY
RECLOSE
OFF
BATTERY
ALT
TEST
PROFILE
INSTALLATION AND OPERATION INSTRUCTIONS MN280048EN June 2016
SPEAR™ Single-Phase Recloser System
The
(left) key is used to go up one Menu level.
●
●
The
(left) key is used to move left when editing
●
●
parameters.
The
(right) key is used to go down one Menu level.
●
●
The
(right) key is used to move right when editing
●
●
parameters.
The ESC (escape) key is used for the following tasks:
G163 .0
●
●
Go back one Menu level
●
●
Cancel Edit mode when editing settings without
●
●
changing the value
The ENTER key is used for the following tasks:
●
●
Go down one Menu level
●
●
Confirm settings change in the Edit mode
●
●
Confirm resetting the Resettable Parameters
●
●
Confirm passwords
●
●
The EDIT key is used for the following tasks:
●
●
Enter the Edit mode to make a change.
●
●
Enter the Reset mode to reset the Resettable
●
●
Parameter
Status indicator LEDs
The status indicator LEDs (Figure 4 and Figure 5) in the
Programming section of the Operator Panel give instant
information on the control and recloser status:
This information is indicated on the left side of the control:
(Figure 4):
PHASE FAULT: This LED illuminates when the control
●
●
issues an overcurrent trip signal while the phase current
exceeds the programmed minimum trip value.
ABOVE MIN TRIP: This LED illuminates when the control
●
●
detects that current is above the programmed minimum
trip value.
LOCKOUT: This LED illuminates to indicate the control is
●
●
in a locked out state, i.e. a reclosing sequence is not in
progress. This LED does not indicate that the recloser is
open.
Hazardous voltage . Do not rely on the open position
of the yellow operating handle on the recloser or the
OPEN or LOCKOUT LED indicators on the recloser
control; it does not ensure that the line has been
de-energized . Always establish a visible disconnect .
Failure to follow proper safety practices can result in
contact with high voltage, which will cause death or
severe personal injury .
WARNING
G171 .0
5