12. Perform a battery test on the new battery (assuming it
has been adequately charged) to confirm the state of
the new battery and wire assembly connections. Refer
to the Battery test and charging procedures section.

Return the control to service

After the required work is completed, proceed as follows:
1.
Remove AC power from the control.
2.
Disconnect the control battery.
3.
Disconnect the control from the test set.
Follow this procedure to return the control to service:
1.
Appropriate personnel must verify that all control
settings are correct.
2.
Reconnect the ground cable to the control.
3.
Control cable properly connected, fully tightened to
ensure gasket seal, and supported on both ends.
4.
Plug in the control battery.
The SPEAR single-phase recloser control will not
N
otee:
automatically power up until AC power is applied.
5.
Apply AC power to the control.
6.
Verify the control clock is set to the current time after
AC power has been reapplied.
The control clock may require resetting if the
N
otee:
operating power has been disconnected for more
than thirty days. Refer to Service Information
MN280012EN SPEAR Single-Phase Recloser Control
Programming Guide for information on setting the
control clock.
Wing
nut
Figure 44 .
Reinstall wing nuts and battery bracket
Wing
nut
Wing
nut
INSTALLATION AND OPERATION INSTRUCTIONS MN280048EN June 2016
SPEAR™ Single-Phase Recloser System

Additional information

CAUTION
This equipment requires routine inspection and
maintenance to ensure proper operation . If it is not
maintained, it can fail to operate properly . Improper
operation can cause equipment damage and possible
personal injury .

Replacement kits

Replacement parts kits for the SPEAR single-phase
recloser control are available through the factory Service
Department. Only factory-authorized parts are to be used.
To order replacement parts, refer to Parts Guide S260-01
through S280-01 for catalog numbers. Contact your Eaton
representative for additional information and ordering
procedures.

Factory-authorized service centers

Factory-authorized service centers are located throughout
the continental United States to provide maintenance, repair
and testing services for Eaton's Distribution Switchgear
products. Refer to Service Centers Brochure B100-04009 for
the Authorized Service Center closest to your location. For
further information, contact your Eaton representative.

Factory maintenance classes

The factory service department offers a basic testing
and troubleshooting course for the SPEAR single-phase
recloser system. This course, taught by experienced
service technicians, is held at the factory's in-house training
facility. For additional information, contact your Eaton
representative.

Type MET recloser control tester

A 30-minute video program KSPV7 Kyle Type MET Electronic
Recloser Control Tester Operation and Testing Procedures
is available as a supplemental training aid for service
personnel.
G105 .1