SPEAR™ Single-Phase Recloser System
4.
Ground the recloser. Make ground connections to the
recloser head ground connector. It will accommodate
#8 solid to 2/0 stranded conductors.
This recloser is used in conjunction with an Eaton's
Cooper Power series SPEAR single-phase recloser
control. Refer to the Grounding the control section
of this manual for comprehensive recommended
grounding instructions.
5.
Ground the mounting hanger. Make ground connections
in accordance with approved utility standards.
Position A
Acceptable module rotations
Position C
Unacceptable module rotations
*Position B is the factory shipment assembly.
Figure 12 .
Module rotations
14
INSTALLATION AND OPERATION INSTRUCTIONS MN280048EN June 2016
Position B*
Figure 13 .
pole mounting
6.
Position D
7 .
N
otee:
14.68 [373]
9.68 [246]
SOURCE
12.72 [323]
VIEW AS SHIPPED
0.50 MOUNTING BOLT
7.34 [186]
14.68 [373]
9.68 [246]
9.68 [246]
SOURCE
VIEW WITH HEAD ROTATED 90
NOTES:
1. CUSTOMER TO PROVIDE ARRESTER AS REQUIRED
2. ARRESTER SHOWN IS A COOPER UltraSIL HOUSED
VariSTAR SURGE ARRESTER (15 kV)
3. ARRESTER MOUNTING BRACKETS ACESSORY
ORDERED SEPARATELY (SHOWN ABOVE).
DIMENSIONS IN [ ] ARE IN MILLIMETERS
Rotation of SPEAR single-phase recloser for
Install the SPEAR single-phase recloser control.
Connect the control cable between the control and
the recloser. Make sure the control is grounded and
properly programmed for the planned installation.
To ensure proper installation of this cable, securely
fasten the cable coupler ring (Figure 14).
Make the high-voltage line connections. See Figure 15.
Disconnect switches and bypass switches are
recommended to facilitate switching and isolation.
14.68 [373]
9.68 [246]
LOAD
9.44 [240]
LOAD
7.34 [186]
0. 5 0 MOUNTING
BOLT
14.68 [373]
12.72 [323]
o