Alarm condition
During a battery test a 5Ω, 55 watt resistor is placed across
the battery terminals for approximately 5 seconds. The
SPEAR single-phase recloser control measures the battery
voltage, if the voltage drops below 22.8 VDC the BATTERY
LED illuminates (Figure 37) and a battery alarm is issued, if
configured, at the end of the test.
ALARM
CONTROL OK
AC POWER
BATTERY
Figure 37 .
Control OK and AC POWER LEDs

Remove the control from service

Disconnect switches for AC sensing and power connections
are necessary to isolate the SPEAR single-phase recloser
DATA PORT
control for testing and servicing.
SUPER-
NON
Hazardous voltage . Open CT secondaries can
VISORY
generate high voltages . Contact with CT pins of the
RECLOSE
OFF
disconnected cable can cause electric shock and may
result in personal injury . Open recloser contacts and
open disconnect switches before disconnecting
BATTERY
control cable .
ALT
TEST
PROFILE
Hazardous voltage . Cable conductors attached to
controls will remain at 53V DC and 120/240V AC
potential while connected to the control . Contact
with any pins at the end of the cable directly or
indirectly connected to a control can result in personal
injury or equipment damage . Disconnect battery and
external power sources in the control then remove
control cable at control end before disconnecting from
recloser end .
1.
Disconnect the 24 V control battery.
2.
Disconnect control cable from control.
3.
Remove control AC sensing and power connections
from the control.
IMPORTANT
CAUTION
CAUTION
INSTALLATION AND OPERATION INSTRUCTIONS MN280048EN June 2016
4.
Disconnect any serial communications port connection
(Figure 38).
5.
Disconnect the ground from the control.
6.
Carefully transport the control to a suitable service
facility.
Figure 38 . Side swing-panel view of SPEAR single-
phase recloser control

Preliminary testing with no AC available

If the SPEAR single-phase recloser control is not in service
and requires energization for preliminary testing, it can be
powered up with battery power only.
1.
Open the swing panel and locate the pushbutton switch
recessed inside the control side panel (Figure 39).
2.
Momentarily (4-5 seconds) press the switch with a
non-conductive tool (Figure 39). The control will power
T204 .3
up.
3.
To power down the SPEAR single-phase recloser
control, unplug the battery (disconnect the black/red
battery connector).
4.
Perform a battery charging cycle. Refer to Battery
charging in the Battery test and charging procedures
section of these instructions.
While the SPEAR single-phase recloser control is powered
in this manner, the control battery is being continuously
T312 .3
discharged. When the battery voltage drops below 21V DC
for 60 seconds, the control will automatically power down.
If the battery is left in a discharged condition, the battery(s)
will sustain permanent irreversible damage. Therefore, a
battery charging cycle should always be performed after this
procedure to bring the battery(s) back up to full charge.
SPEAR™ Single-Phase Recloser System
IMPORTANT
37