Configuring I/O Channels - Siemens TM Timer DIDQ Commissioning Manual

Motion control technology modules for simotion scout and simotion scout tia
Table of Contents

Advertisement

Configuring
3.2 SIMOTION SCOUT
3.2.4.2

Configuring I/O channels

Procedure
To configure I/O channels as measuring input input (Timer DI) and output cam (Timer DQ) in
the TM Timer DIDQ 10x24V technology module, proceed as follows.
1. Select the ET 200SP interface module in HW Config in the station window. Open the
"Properties" dialog by double-clicking on the TM Timer DIDQ 10x24V technology module
in the detail view.
2. You can configure the channels in the "Properties" dialog box of the technology module
under the "Parameters" tab.
3. In the example, select the value "Use input/output individually" for the DQ0 / DI0 channel
group from the "Configuration DQ/DI group" drop-down list. This allows the channels DQ0
and DI0 to be parameterized and used independently of one another.
Figure 3-9
Note
This setting allows channel DQ0 to be interconnected as output cam and DI0 as measuring
input under SIMOTION SCOUT.
32
Configuring the TM Timer DIDQ 10x24V technology module
Technology Modules TM Timer DIDQ for SIMOTION SCOUT and SIMOTION SCOUT TIA
Commissioning Manual, 01/2015