Configuring
3.2 SIMOTION SCOUT
● Identification tab
– Plant ID of the module
– Location ID of the module
– Date on which the module was installed.
– Further information: Free text, which is stored in the module.
● Parameters tab
In this tab you parameterize the module, for example the configuration of the DQ/DI groups
(see Setting options for TM Timer DIDQ 10x24V technology module (Page 30)).
Configuring PROFINET communication
Preconditions
1. The respective ET 200SP interface module is initialized.
2. The ET 200SP interface module is integrated into the topology (prerequisite for operation
in IRT mode).
3. The controller is configured as sync master (prerequisite for operation in IRT mode).
Note
For further information on configuration of the PROFINET communication please refer to the
SIMOTION SCOUT Communication or SIMATIC Communication Manuals.
Operating the ET 200SP interface module and TM Timer DIDQ technology module in IRT mode
For use of the channels as cam output or measuring input input, the module must be
synchronized with the controller (IRT mode).
To configure PROFINET communication on the PN interface module ET 200SP and on the
TM Timer DIDQ technology module in IRT mode, please proceed as follows:
1. Configure the PROFINET IO topology.
2. Select the ET 200SP interface module in HW Config.
3. Select the PN IO line in the detail view of HW Config. Double-click to open the "Properties
- PN IO" dialog box.
28
Technology Modules TM Timer DIDQ for SIMOTION SCOUT and SIMOTION SCOUT TIA
Commissioning Manual, 01/2015