3 Setting up and commissioning the application
3.5 Loading the software
No.
Action
13.
If the used SINAMICS drive has a
safety configuration, please also
reset it.
In "Restore factory setting"
1.
you choose the "Safety
parameters will be reset"
option.
2.
Start the function.
3.
Enter the previous Safety
password.
4.
Confirm with OK.
14.
1.
Disconnect the online
connection to SINAMICS
drive.
2.
Saving the data to EEPROM
is not necessary at present.
15.
Load the drive configuration into
the SINAMICS G120.
SINAMICS G120 DP at S7-1200
Entry-ID: 70155469,
V1.4,
07/2018
Remarks
All Safety parameters will be reset
1
2
4
1
3
2
15