Siemens SINAMICS S Series List Manual page 183

Hide thumbs Also See for SINAMICS S Series:
Table of Contents

Advertisement

p0445[0...n]
Encoder commissioning serial number part 5 / Enc comm ser_no 5
SERVO, VECTOR
Can be changed: C2(4)
Data type: Unsigned32
P-Group: Encoder
Not for motor type: -
Min
0000 hex
Description:
Serial number part 5 of the encoder for the commissioning.
Dependency:
Refer to: p0440, p0441, p0442, p0443, p0444, r0460, r0461, r0462, r0463, r0464
Refer to: F07414
Note:
A value of zero is displayed if an encoder is not present.
p0446[0...n]
Encoder SSI number of bits before the absolute value / Enc SSI bit before
SERVO, VECTOR
Can be changed: C2(4)
Data type: Unsigned16
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Sets the number of bits before the absolute value in the SSI protocol.
Note:
For example, error bit, alarm bit or parity bit can be positioned at these bits.
p0447[0...n]
Encoder SSI number of bits absolute value / Enc SSI bit val
SERVO, VECTOR
Can be changed: C2(4)
Data type: Unsigned16
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Sets the number of bits for the absolute value in the SSI protocol.
p0448[0...n]
Encoder SSI number of bits after the absolute value / Enc SSI bit after
SERVO, VECTOR
Can be changed: C2(4)
Data type: Unsigned16
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Sets the number of bits after the absolute value in the SSI protocol.
Note:
For example, error bit, alarm bit or parity bit can be positioned at these bits.
p0449[0...n]
Encoder SSI number of bits, filler bits / Enc SSI fill bits
SERVO, VECTOR
Can be changed: C2(4)
Data type: Unsigned16
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Sets the number of filler bits for double absolute value transfer in the SSI protocol.
Dependency:
Refer to: p0429
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Calculated: CALC_MOD_ALL
Dynamic index: EDS, p0140
Units group: -
Max
FFFF FFFF hex
Calculated: -
Dynamic index: EDS, p0140
Units group: -
Max
65535
Calculated: -
Dynamic index: EDS, p0140
Units group: -
Max
65535
Calculated: -
Dynamic index: EDS, p0140
Units group: -
Max
65535
Calculated: -
Dynamic index: EDS, p0140
Units group: -
Max
65535
Parameters
List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 hex
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
25
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
1-183