Grounding The Dc System; Figure 3-6 Chassis Ground Lug Location On Inverter Dc End - Xantrex SW Plus 2524 Owner's Manual

Sine wave plus inverter/charger
Table of Contents

Advertisement

Grounding the DC System

976-0043-01-02
WARNING: Fire Hazard
Undersized cables can overheat and melt creating a fire hazard when subjected to
heavy (peak) loads. Always use a properly sized cable and length rated for the
amperage of the inverter and batteries.
WARNING: Shock Hazard
Always attach ground leads before attaching AC or DC power connections.
The inverter's chassis ground lug (see
chassis of the inverter to the DC grounding system. The terminal accepts
wires from #14 AWG to #2 AWG.
Chassis
Ground Lug

Figure 3-6 Chassis Ground Lug Location on Inverter DC End

The Xantrex DC175 and DC250 have optional grounding blocks to
simplify grounding procedures and can be used as the DC disconnect as
shown in
Figure 3-7 on page
Figure
3-6) is used to connect the
DC End of Inverter
3–16.
DC Wiring
3–15