Inverter Specifications

Inverter Capacity versus Temperature

A–12
The output power of the inverter diminishes as ambient temperature rises.
However, as can be seen below, with the exception of the SWP5548, these
inverters are sized to be able to run a full rated output power up to 40C.
However, it should be noted that the overcurrent circuit on the unit is
temperature compensated to protect the unit and that the thermal circuit
breaker will trip at a lower current as the temperature rises. Therefore, the
surge ability of the unit decreases with increased temperature.
Table A-1 Derating from continuous power (VA) at elevated ambient
temperatures
M o d e l
2 5 ° C
SW Plus 2524
No Derating
SW Plus 2548
No Derating
SW Plus 4024
No Derating
SW Plus 4048
No Derating
SW Plus 5548
No Derating
This table refers to output VA only. Testing was conducted in a thermal
chamber with the inverters as stand-alone units without accessories.
3 0 ° C
3 5 ° C
No Derating
No Derating
No Derating
No Derating
No Derating
No Derating
No Derating
No Derating
No Derating
No Derating
4 0 ° C
No Derating
No Derating
No Derating
No Derating
5.3KVA
976-0043-01-02