Master Bilt MCR-33101 Installation & Operation Instructions page 43

Blast chiller
Hide thumbs Also See for MCR-33101:
Table of Contents

Advertisement

PRE-COOLING START-UP
Every operating cycle can be preceded by pre-cooling.
Operate as indicated to start pre-cooling:
1. Make sure the device is in the "ON" status.
2. Make sure that the keyboard is not locked and that no
procedure is in progress.
3. Press and release the key (1) and then press and
release the START/STOP key (2).
4. The cycle can be stopped at any time by pressing and releasing the START/STOP key.
Parameter r120 establishes the work set-point during pre-cooling.
When the cabinet temperature reaches that established with parameter r12, pre-cooling continues, and
the buzzer is activated for 2s to indicate that the pre-cooling cycle has been completed.
SWITCHING ON UV LIGHT FOR STERILIZATION CYCLE (if available)
Operate as follows:
1. Make sure that parameter u11 is set at 2.
2. Make sure the device is in the "ON" status and that
the door is closed, the door switch is not active.
3. Make sure that the keyboard is not locked and that no
procedure is in progress.
4. Press and release the key (1), press and release the
key (2) and then press and release the START/STOP
key (3). The device will display the residual time of
the UV light switch-on duration and the cabinet
temperature.
The UV light is switched on for the time period established by parameter u6; opening the door i.e. the
activation of the door micro switch causes the light to switch off.