When the temperature detected by the needle probe
reaches the end temperature of the soft deep freezing
phase, the device automatically passes to deep freezing.
If the temperature detected by the needle probe reaches
the deep freezing end temperature within the maximum
deep freezing duration, it means that deep freezing has
been completed successfully, the device will
automatically pass to storage and the buzzer will be
activated for the period of time established with
parameter AA to indicate that the cycle has been
completed.
If the temperature detected by the needle probe does not
reach the deep freezing end temperature within the
maximum deep freezing duration, deep freezing will not
be completed successfully but will continue and the
buzzer will be activated. Press and release a key to
restore normal display and to silence the buzzer.
When the temperature detected by the needle probe
reaches the deep freezing end temperature, the device
automatically passes to storage in the same way as
illustrated previously.