10. SETTING AND OPERATION
10.1 OPERATION MODES
1
7
6
1 Bar display of values
2 Numerical display of values
3 Unit display of the currently selected parameter
4 Display of the currently selected mode
5 + key
6
key
7 - key
10.2 SWITCHING THE PUMP ON AND OFF
operate with factory settings, i.e. in automatic mode
the last settings that were set prior to its last shut-down
5 seconds, until OFF is shown on the display. Once the
pump is switched off, the OFF sign will remain visible
on the numerical display
10.3 BUTTONS
- Key
Short key press:
> To scroll downwards through parameters
> To scroll downwards through operating modes
> To decrease parameter values
Long key press:
> 3 seconds, along with the + key to select night mode
> 5 seconds to switch off the pump
> 5 seconds, along with
to factory settings.
Key
Short key press:
> To confirm currently selected value
Long key press:
> 3 seconds, to activate operating mode selection
> 5 seconds, along with long key presses on
keys to reset pump to factory settings.
2
3
5
4
- key for
- key
and + keys to reset pump
and -
+ Key
Short key press:
> To scroll upwards through parameters
> To scroll upwards through operating modes
> To increase parameter values
Long key press:
> 3 seconds, along with the - key to select night mode,
> 5 seconds, along with
to factory settings.
10.4 SETTINGS
hold the
key for 3 seconds and select the desired
operating mode of the pump with + or - keys. Confirm
the selection with the
Once the operating mode is confirmed, the display shows
the settable parameter (not valid for automatic mode)
keys and confirm the setting with the
pressing + and - keys and holding them for 3 seconds
/h, rpm) navigate with + and - keys.
3
(W, m, m
11. OPERATING MODES DESCRIPTION
The pump can operate in 4 different operating modes.
Depending on the system in which the pump operates, the
pump can be set in the most appropriate mode.
Pump modes:
Each mode can coexist with the night mode
A
Automatic mode (factory setting)
In automatic mode, the pump automatically sets its operating
pressure according to the status of the hydraulic system.
By doing so, the pump automatically finds the optimal
operating position.
This mode is recommended in most systems. The parameters
cannot be set; they can only be scrolled through.
Proportional pressure
In this mode the pump continually
regulates the head based on the flow
rate, by varying the pressure in linear
fashion within the maximum to minimum
range. The value to be set (Hset on the
drawing) corresponds to the maximum
pressure at maximum power; at 0 flow
the pressure will be equivalent to 50% of the pressure
set (Hset/2). Between these two values, the pressure will
change linearly, in relation to the flow.
In this mode only the pump pressure can be set (Hset
on the drawing); the remaining parameters can only be
scrolled through.
Constant pressure
In this mode the pump maintains the
currently set pressure (Hset on the
drawing) constant, regardless from the
demand of the system (from 0 flow to
maximum power, at which point the
and - keys to reset pump
key
+ and -
key