6. TECHNICAL AND BUILDING FEATURES
6.1 TECHNICAL DATA
Ego (T) (C) easy - Ego (B) easy
Pump type
Power P
1
Rated current I
n
Power Supply
Motor protection
GB
Protection class
Insulation class
Relative humidity
Ambient temperature
Medium temperature
System pressure
6.2 LIMITS OF USE (Valid for Ego (T) (C) easy models)
The minimum pressure at suction shall be:
- 0.05 bar for medium at 50°C
- 0.80 bar for medium at 80°C
- 1.40 bar for medium at 110°C
Ambient and medium temperature:
Ambient
Temperature [°C]
Up to 25°C
30°C
35°C
40°C
Working outside of recommended conditions
can shorten life time and nullify the warranty
7. INSTALLATION, DISMANTLING
AND TRANSPORT
7.1 GENERAL ARRANGEMENT FOR INSTALLATION
in horizontal position (fig. 3.1). Allowed and forbidden
positions are shown in fig. 3.2
flow
control box can be rotated so that the connector is in
a horizontal position
the motor is not allowed (see Figure 3.3c)
off valves on the pressure and suction side of the pump
and unscrew the screws (Figure 3.3). Turn the electric
motor part as shown in Figures 3.3a or 3.3b.
7.2 DISMANTLING
In order to handle and dismantle the electropump you should:
a) Take off the power supply.
b) Lift the electropump with suitable means according to
its weight and dimensions
8
xx-120
xx-100
xx-80
10-180W 10-180W 10-140W 10-90W
0,1-1,5A 0,1-1,5A 0,1-1,15A 0,1-0,75A
1~230V – 50/60Hz
External protection is not necessary
IP44
F
Max 95%
0÷40°C
2÷110°C (5÷65°C for Ego B easy)
Up to 1 MPa (10 bar)
Medium Temperature
min. [°C]
max. [°C]
2
110
2
100
2
2
7.4. TRANSPORT
The electropump is packed in a carton or, depending on
its weight and dimensions, it is fixed on a wooden pallet;
however, transport does not present many difficulties.
In any case, check the total weight imprinted on the box.
xx-60
8.
ELECTRICAL CONNECTION
8.1. PROTECTIVE DEVICES
ACCORDING TO THE LAW BY A QUALIFIED TECHNICIAN.
TO THE EARTH OF THE PLANT ACCORDING TO
THE ELECTRICAL STANDARDS IN FORCE IN YOUR
COUNTRY: THE INSTALLER SHALL BE THE SOLE
RESPONSIBLE FOR IT.
WE RECOMMEND INSTALLING A HIGH SENSITIVE
DIFFERENTIAL SWITCH (0.03 A).
After installing the unit check again the feeding cable
following the CABLE CONNECTION instructions and
connect it to the control panel (1) that must be fitted,
according to the actual rules, with:
90
8.2. CABLE CONNECTION
80
connector. Its mounting instructions are shown in the
picture accompanying the connector.
50 Hz) must be carried out with suitable standardised
connecting cord
in contact with the casing of the device, due to the high
temperatures of the casing.
9. USE AND RUNNING
fluid and to vent the system
as this occurs automatically when the hydraulic system
is being ventilated during the start-up. The air in the
pump generates noise. After a short working period
noise should disappear.
must be guaranteed (see LIMIT OF USE)
During its running, it is normal for the pump to
heat up, or to be heated by the pumped fluid - to
prevent from risk of burns, it should therefore
not be touched!
3.1, detail A) between the hydraulic housing and the
electric motor housing should not be insulated, since
the thermal insulation might hinder cooling and drainage
of condensate from the pump's motor housing.
the net (minimum opening contacts 3 mm).
magnetothermics, rated in compliance with the
current plate.
dissipations, lack of water, atmospheric discharges
and functioning-failure indicators.
IMPORTANT: ALL THE ELECTRIC MASSES MUST
BE CONNECTED TO THE EARTH OF THE PLANT.
go (B) easy do not need to be manually vented,

Advertisement