2. Reinstall your eXFlash IPMI Proxy Service.
3. Perform a full AC power cycle on the system.
4. If the node has recently been installed, moved, serviced, or upgraded, verify that the eXFlash
DIMM is properly seated and visually verify that there is no foreign material in any DIMM
connector on that memory channel. If either of these conditions is found, correct and retry with
the same eXFlash DIMM. (Note: Event Log may contain a recent 00580A4 event denoting
detected change in DIMM population that could be related to this problem.)
5. Check IBM support site for an applicable service bulletin or firmware update that applies to this
eXFlash error.
6. If problem persists and there are no other eXFLash DIMMs with the same indication, confirm that
the eXFlash DIMM is under warranty before replacement.
7. Replace compute book.
8. (Trained Service technician only) Replace affected Processor.
Related links
– Server features and specifications
– Removing a compute book
– Replacing a compute book
– Removing the compute book cover
– Replacing the compute book cover
– Removing a memory module
– Replacing a memory module
– eXFlash DIMMs
• 806f010d-2b84000c : The [NumericSensorElementName] has been disabled due to a detected fault.
The eXFlash Proxy Service detected a fault on the eXFlash DIMM 12 in Compute Book 4.
May also be shown as 806f010d2b84000c or 0x806f010d2b84000c
Severity
Error
Serviceable
Yes
Automatically notify support
Yes
Alert Category
Critical - Hard Disk drive
SNMP Trap ID
5
CIM Information
Prefix: PLAT ID: 0164
User Response
1. Verify that the most recent eXFlash DIMM firmware and eXFlash IPMI Proxy Service are installed.
2. Reinstall your eXFlash IPMI Proxy Service.
3. Perform a full AC power cycle on the system.
4. If the node has recently been installed, moved, serviced, or upgraded, verify that the eXFlash
DIMM is properly seated and visually verify that there is no foreign material in any DIMM
connector on that memory channel. If either of these conditions is found, correct and retry with
the same eXFlash DIMM. (Note: Event Log may contain a recent 00580A4 event denoting
detected change in DIMM population that could be related to this problem.)
830
System x3850 X6 and x3950 X6 Installation and Service Guide