Table of Contents

Advertisement

Quick Links

System x x3850 X6 and x3950 X6 Data Center Planning
v1.0.3
FAST, AGILE, RESILIENT
The sixth generation of
Enterprise X-Architecture
technology, the X6 servers
are fast in application
performance, has an agile
design and is a
resilient platform that
maximizes up time.
CHOICE & FLEXIBILITY
The x3850 X6 server
supports up to four
redundant power supplies,
and the x3950 X6 up to eight
redundant power supplies,
offering 750W, 900W or
1400W capacities to meet
your environmental needs.
SUPERIOR COOLING
The systems provide
Calibrated Vectored
Cooling™, with up to ten
redundant hot-swap fan
packs and five fan zones with
N+1 fan redundancy per
node. Each fan pack includes
two counter-rotated dual-
motor fans.

Advertisement

Table of Contents
loading

Summary of Contents for Lenovo x3840 X6

  • Page 1 System x x3850 X6 and x3950 X6 Data Center Planning v1.0.3 FAST, AGILE, RESILIENT CHOICE & FLEXIBILITY SUPERIOR COOLING The sixth generation of The x3850 X6 server The systems provide Enterprise X-Architecture supports up to four Calibrated Vectored technology, the X6 servers redundant power supplies, Cooling™, with up to ten are fast in application...
  • Page 2 Updates to format, contacts, webpage, and email. 1.0.2 – April 21 , 2015 Update to template 1.0.3 May 22 , 2015 Convert to Lenovo logo IMM2 Contributors: Jerrod Buterbaugh, System x Data Center Services Reviewers: Matthew Archibald, System x Data Center Services...
  • Page 3: Table Of Contents

    Table of Contents ......................5 NTRODUCTION About This Guide....................5 X6 S .................6 YSTEM X YSTEM OWER VERVIEW X6 S (PSU)............6 YSTEM X YSTEM OWER UPPLY 900W AC PSU – Rating & Part Number Information..........6 1400W AC PSU – Rating & Part Number Information..........6 750W DC PSU –...
  • Page 4 N+N and N+1 Examples..................96 IEC 320 C ....................97 ONNECTORS IEC 320 C ....................98 ONNECTORS IEC 309 P & S .................99 LEEVE ECODE (IP) D ................100 NGRESS ROTECTION ECODE 60A T ............100 HREE HASE ELTA OWER ALCULATIONS 50A T ............101 HREE HASE ELTA OWER...
  • Page 5: Introduction

    Introduction The System x X6 servers are the sixth generation of servers built upon the System x Enterprise X-Architecture. Enterprise X-Architecture is the culmination of bringing generations of System x technology and innovation derived from our experience in high-end enterprise servers. The System x X6 generation server pack numerous fault-tolerant and high-availability features into a high-density, rack-optimized, chassis-like package where all serviceable components are front and rear accessible, significantly reducing the...
  • Page 6: System X X6 System Power Overview

    System x X6 System Power Overview Use the Power Configurator at the link below to estimate power consumption and heat load for System x X6 configurations. http://www.ibm.com/support/entry/portal/docdisplay?lndocid=LNVO-PWRCONF System x X6 System Power Supply Unit (PSU) The following tables represent the technical specifications of the compatible PSUs for the x3850 X6 and x3950 X6 servers.
  • Page 7 Depending on your load and power requirements, the x3850 X6 supports the following power supply installation:  One 900W  One 1400W  Two 900W  Two 1400W  Two 900W and two 1400W  Four 900W  Four 1400W ...
  • Page 8: Plus

    80 PLUS 80 PLUS is a performance specification for power supplies used within servers and computers. To meet the 80 PLUS standard, the power supply must have an efficiency of 80% or greater, at 20%, 50%, and 100% of rated load with PF of 0.9 or greater. The standard has several grades, such as Bronze, Silver, Gold, Platinum, and Titanium.
  • Page 9: X6 Power Supplies

    X6 Power Supplies The following section covers the x3850 X6 and x3950 X6 power supplies unit (PSU) installation order and placement rules. Input feed wiring for redundancy is also discussed. x3850 X6 Power Supply Placement The power supplies are labeled from left to right when viewed from the rear of the server and are grouped in pairs as seen in the following picture.
  • Page 10: 3950 X6 Power Supply Placement

    x3950 X6 Power Supply Placement The power supplies are labeled from left to right when viewed from the rear of the server and are grouped in pairs as seen in the following picture. Group A (blue) consists of PSU bay 1, 3, 5 and 7 and Group B (green) consists of PSU bay 2, 4, 6 and 8.
  • Page 11: Power Supply Installation And Ordering

    Power Supply Installation and Ordering The following rules apply when installing 1, 2, and 4 AC and DC PSUs in the x3850 X6 system.  For a 1 PSU installation, install the PSU in bay 3. Fillers must be installed in bays 1, 2, and 4.
  • Page 12: Power Supply Input Feed Wiring For Redundancy

    In a 4 PSU configuration, mixing of 900W PSUs and 1400W PSUs is allowed. The following rules apply when mixing PSUs.  A mixture of 900W and 1400W PSUs must be installed in group A and group B. Example:  Bay 1 (group A) = 900W ...
  • Page 13 Example of input feed wiring for 2 x 1400W PSUs: Feed 1 Feed 2 PS 2, Bay 2 PS 1, Bay 3 1400W 1400W PS 3, Bay 1 PS 4, Bay 4 Empty Empty Group A Group B Example of input feed wiring for 4 x 900W PSUs: Feed 1 Feed 2 PS 2, Bay 2...
  • Page 14: Imm2 Power Policies

    IMM2 Power Policies As previously mentioned, the IMM2 code controls the x3850 X6 and x3950 X6 power policy. The servers support three modes of redundancy based on the power supply configuration, system load and the Power Policy configuration controlled by the IMM2: ...
  • Page 15: Setting A Power Policy

    Setting a Power Policy The default power policy configuration setting for both AC and DC models is Non- Redundant with Throttling enabled. This is to ensure the server will boot the first time regardless of the installed hardware or if you have not yet implemented a power policy.
  • Page 16: Imm2 Power Capping And Power Monitoring

    IMM2 Power Capping and Power Monitoring The 'Server Management Power' page in the IMM2 settings allows for power capping (throttling) and power allocation and monitoring of the X6 hardware to help manage the systems power usage and consumption. The following sections discusses both of these features of the IMM2.
  • Page 17: Power Monitoring And Power Allocation

    Power Monitoring and Power Allocation The 'Server Power Management' page contains information on the power supply utilization and the DC power consumption of your server. The below image is a screen shot of this page from the IMM2. The wattage calculated for the power supply utilization and the DC power consumption is only the theoretically amount of power that all components installed in your server could potentially consume.
  • Page 18: Power History

    Power History The 'Server Power Management' page contains information on the history of your power consumption. This is found under the 'Power History' tab. The below images are screen shots of a servers power history in chart and table format. You can view the history of the servers AC or DC power consumption in minutes, hours or days.
  • Page 19: System X Power Maximizer

    System x Power Maximizer System x Power Maximizer is an integrated software tool for determining the as- configured total power budget for all new System x, Pure Flex, iDataPlex, and NeXtScale systems. This technology takes a more granular approach of determining system and chassis power budget than using look-up tables in system management devices.
  • Page 20: System X Power Configurator

    System x Power Configurator The System x Power Configurator is a software tool designed to assist with calculating System x Systems environmental information. The data in the System x Power Configurator tool is derived from running real-world workloads across a number of configurations to properly characterize component power consumption under various conditions.
  • Page 21: System X X6 Pdu And Line Cord Selection

    System x X6 PDU and line cord selection Some PDUs have attached line cords while others require a line cord to be ordered separately based on your requirement of Three-phase power or Single-phase power. Refer to the following table for line cord and phase options for both North America and International PDUs.
  • Page 22: Switched And Monitored Pdus - International

    Part Description Line cord Phase Voltage Line cord Line cord Number / Number part (ph) rating plug Type of number (Derated) outlet Switched and Monitored PDUs - International 46M4119 System x 0U 24 C13 Attached 220V- IEC 309 24 / C13 Switched and 240V P+N+G...
  • Page 23: Enterprise Pdus - North America

    Part Description Line cord Phase Voltage Line cord Line cord Number / Number part (ph) rating plug Type of number (Derated) outlet Enterprise PDUs - North America 71762NX System x Ultra 40K9614 200V- 30A (24A) NEMA 9 / C19 Density 240V L6-30P 3 / C13...
  • Page 24: Enterprise Pdus - International

    Part Description Line cord Phase Voltage Line cord Line cord Number / Number part (ph) rating plug Type of number (Derated) outlet Enterprise PDUs - International 71762NX System x Ultra 40K9612 220V- IEC 309 9 / C19 Density 240V P+N+G 3 / C13 Enterprise 1U PDU 40K9613...
  • Page 25 Part Description Line cord Phase Voltage Line cord Line cord Number / Number part (ph) rating plug Type of number (Derated) outlet 39Y8941 DPI Single Phase 40K9612 220V- IEC 309 12 / C13 C13 Enterprise 1U 240V P+N+G PDU without line 40K9613 220V- IEC 309...
  • Page 26: Front-End Pdus - North America

    Part Description Line cord Phase Voltage Line cord Line cord Number / Number part (ph) rating plug Type of number (Derated) outlet Front-end PDUs - North America 39Y8938 30 amp/125V Included 125V 30A (24A) NEMA 3 / C19 Front-end PDU L5-30P 39Y8939 30 amp/240V...
  • Page 27: Universal Rack Pdus

    Part Description Line cord Phase Voltage Line cord Line cord Number / Number part (ph) rating plug Type of number (Derated) outlet Universal Rack PDUs 39Y8951 DPI Universal Rack Included 200V- IEC 320 7 / C13 PDU with US LV 240V C19 to and HV LC...
  • Page 28 Part Description Line cord Phase Voltage Line cord Line cord Number / Number part (ph) rating plug Type of number (Derated) outlet 2.5m Optional line cord 39M529 4.3m 39Y8956 DPI Universal Rack Included 220V- South Africa 7 / C13 1U PDU with South 250V SABS 164 Africa LC...
  • Page 29 Part Description Line cord Phase Voltage Line cord Line cord Number / Number part (ph) rating plug Type of number (Derated) outlet IRAM 2073 PDU (Argentina) Optional line cord 39M5341 1.8m Optional line cord 39M5342 2.5m Optional line cord 39M5343 4.3m 39Y8960 DPI Universal Rack...
  • Page 30: Basic Pdus - North America

    Part Description Line cord Phase Voltage Line cord Line cord Number / Number part (ph) rating plug Type of number (Derated) outlet 0U Basic PDUs - North America 46M4128 System x 0U 24 C13 Attached 200V- 30A (24A) NEMA L6- 24 / C13 30A PDU 240V...
  • Page 31: System X X6 Power Cords

    System x X6 Power Cords The power supplies in the X6 system have C14 receptacles as seen in the picture below. This means the power cable used for the PSUs will need to have C13 plugs for the server side. One power cord is required for each PSU that is installed in the X6 server.
  • Page 32: System X X3850 X6 And X3950 X6 North American Power Cords

    The following illustrations are examples of the power cables that can be used. C13 to C14 Power Cable C13 to C20 Power Cable 2 x C13 to C14 Y Cable 2 x C13 to C20 Y Cable System x x3850 X6 and x3950 X6 North American Power Cords These power cords are only used in North America or countries on a similar type power grid to connect the X6 system PSUs directly to NEMA 6-15R and NEMA 5-15R outlets.
  • Page 33: System X X3850 X6 And X3950 X6 International Power Cords

    System x x3850 X6 and x3950 X6 International Power Cords These power cords are used internationally to connect X6 system PSUs directly to outlets for the respective countries or regions. Option Feature Code (FC) P/N Description 6364 1.8m, 10A/250V C13 2P+Gnd (Brazil) 6599 1.8m, 10A/125V C13 2P+Gnd (Brazil) 46M2593...
  • Page 34: Typical Power For Common X3850 X6 Configurations

    Typical Power for Common x3850 X6 Configurations Below are common customer configurations and associated power requirements. Small variations in the server configuration will not have a large impact on the total consumption of power. For more accurate power estimates based on your exact node configuration, please download the System x Power Configurator tool.
  • Page 35 Configuration 2 Power Results 1x x3850 X6 4x E7-4860v2 (130W) 48x 4GB 1.35V DIMMs 4x 2.5” 300GB 15K SAS 2x Single Port HBA 1 x ServeRAID Adapter 4x 1400W PSUs 1. 1. Load Factor 85% represents steady state Linpack, Turbo Mode OFF 2.
  • Page 36 Configuration 4 Power Results 1x x3850 X6 4 x E7-8890v2 (155W) 48 x 4GB 1.35V DIMMs 4 x 2.5” 300GB 15K SAS 2 x Single Port HBA 1 x ServeRAID Adapter 4x 1400W PSUs 1. Load Factor 85% represents steady state Linpack, Turbo Mode OFF 2.
  • Page 37: Customized Pdu Configurations

    PDU configurations please email your questions and configurations to power@ lenovo.com. The appropriate personnel will review and advise on the proper PDU solution which meets the customer’s needs. Completing this step will help minimize the official power review time when the solution becomes a Special Bid.
  • Page 38 4 x 1400W PSUs, AC source redundant (N+N), 100V-127V - North America Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America ...
  • Page 39 4 x 1400W PSUs, AC source redundant (N+N), 200V-220V North America...
  • Page 40 Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America  0U Basic PDUs - North America...
  • Page 41 4 x 1400W PSUs, AC source redundant (N+N), 220V-240V, International Refer to the following tables for PDU options for International  Switched and Monitored PDUs - International  Enterprise PDUs - International  Front-end PDUs - International  0U Basic PDUs - International...
  • Page 42 4 x 1400W PSUs, power supply redundant (N+1), 100V-127V, North America Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America ...
  • Page 43 4 x 1400W PSUs, power supply redundant (N+1), 200V-220V, North America...
  • Page 44 Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America  0U Basic PDUs - North America...
  • Page 45 4 x 1400W PSUs, power supply redundant (N+1), 220V-240V, International Refer to the following tables for PDU options for International  Switched and Monitored PDUs - International  Enterprise PDUs - International  Front-end PDUs - International  0U Basic PDUs - International...
  • Page 46 2 x 1400W PSUs, AC source redundant (N+N), 100V-127V, North America Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America ...
  • Page 47 2 x 1400W PSUs, AC source redundant (N+N), 200V-220V, North America...
  • Page 48 Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America  0U Basic PDUs - North America...
  • Page 49 2 x 1400W PSUs, AC source redundant (N+N), 220V-240V, International Refer to the following tables for PDU options for International  Switched and Monitored PDUs - International  Enterprise PDUs - International  Front-end PDUs - International  0U Basic PDUs - International...
  • Page 50 2 x 1400W PSUs, power supply redundant (N+1), 100V-127V North America Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America ...
  • Page 51 2 x 1400W PSUs, power supply redundant (N+1), 200V-220V North America...
  • Page 52 Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America  0U Basic PDUs - North America...
  • Page 53 2 x 1400W PSUs, power supply redundant (N+1), 220V-240V, International...
  • Page 54 Refer to the following tables for PDU options for International  Switched and Monitored PDUs - International  Enterprise PDUs - International  Front-end PDUs - International  0U Basic PDUs - International...
  • Page 55 1 x 1400W PSUs, non redundant (N), 100V-127V, North America Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America ...
  • Page 56 1 x 1400W PSUs, non redundant (N), 200V-220V, North America...
  • Page 57 Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America  0U Basic PDUs - North America...
  • Page 58 1 x 1400W PSUs, non redundant (N), 220V-240V, International Refer to the following tables for PDU options for International  Switched and Monitored PDUs - International  Enterprise PDUs - International  Front-end PDUs - International  0U Basic PDUs - International...
  • Page 59: Psu Configuration Diagrams

    900W PSU Configuration Diagrams The 900W power supply is covered in the following section for both North America and International connection to supported PDUs. AC source redundancy, power supply redundancy and non-redundant scenarios are covered. For the following figures, the following applies: ...
  • Page 60 4 x 900W PSUs, AC source redundant (N+N), 100V-127V North America Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America ...
  • Page 61 4 x 900W PSUs, AC source redundant (N+N), 200V-220V North America...
  • Page 62 Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America  0U Basic PDUs - North America...
  • Page 63 4 x 900W PSUs, AC source redundant (N+N), 220V-240V International Refer to the following tables for PDU options for International  Switched and Monitored PDUs - International  Enterprise PDUs - International  Front-end PDUs - International  0U Basic PDUs - International...
  • Page 64 4 x 900W PSUs, power supply redundant (N+1), 100V-127V, North America Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America ...
  • Page 65 4 x 900W PSUs, power supply redundant (N+1), 200V-220V, North America...
  • Page 66 Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America  0U Basic PDUs - North America...
  • Page 67 4 x 900W PSUs, power supply redundant (N+1), 220V-240V, International Refer to the following tables for PDU options for International  Switched and Monitored PDUs - International  Enterprise PDUs - International  Front-end PDUs - International  0U Basic PDUs - International...
  • Page 68 2 x 900W PSUs, AC source redundant (N+N), 100V-127V, North America Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America ...
  • Page 69 2 x 900W PSUs, AC source redundant (N+N), 200V-220V, North America...
  • Page 70 Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America  0U Basic PDUs - North America...
  • Page 71 2 x 900W PSUs, AC source redundant (N+N), 220V-240V, International Refer to the following tables for PDU options for International  Switched and Monitored PDUs - International  Enterprise PDUs - International  Front-end PDUs - International  0U Basic PDUs - International...
  • Page 72 2 x 900W PSUs, power supply redundant (N+1), 100V-127V, North America Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America ...
  • Page 73 2 x 900W PSUs, power supply redundant (N+1), 200V-220V, North America...
  • Page 74 Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America  0U Basic PDUs - North America...
  • Page 75 2 x 900W PSUs, power supply redundant (N+1), 220V-240V, International Refer to the following tables for PDU options for International  Switched and Monitored PDUs - International  Enterprise PDUs - International  Front-end PDUs - International  0U Basic PDUs - International...
  • Page 76 1 x 900W PSUs, non redundant (N), 100V-127V, North America Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America ...
  • Page 77 1 x 900W PSUs, non redundant (N), 200V-220V, North America...
  • Page 78 Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America  0U Basic PDUs - North America...
  • Page 79 1 x 900W PSUs, non redundant (N), 220V-240V, International Refer to the following tables for PDU options for International  Switched and Monitored PDUs - International  Enterprise PDUs - International  Front-end PDUs - International  0U Basic PDUs - International...
  • Page 80: 1400W Psu Combination Configuration Diagrams

    900W & 1400W PSU Combination Configuration Diagrams The 900W and 1400W combination power supply configuration is covered in the following section for both North America and International connection to supported PDUs. AC source redundancy, power supply redundancy and non-redundant scenarios are covered. For the following figures, the following applies: ...
  • Page 81 2 x 900W & 2 x 1400W PSUs, AC source redundant (N+N), 100V-127V North America Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America ...
  • Page 82 2 x 900W & 2 x 1400W PSUs, AC source redundant (N+N), 200V-220V North America...
  • Page 83 Refer to the following tables for PDU options for North America  Switched and Monitored PDUs - North America  Enterprise PDUs - North America  Front-end PDUs - North America  0U Basic PDUs - North America...
  • Page 84 2 x 900W & 2 x 1400W PSUs, AC source redundant (N+N), 220V-240V, International Refer to the following tables for PDU options for International  Switched and Monitored PDUs - International  Enterprise PDUs - International  Front-end PDUs - International ...
  • Page 85: System X North American Pdus Line Cords

    System x PDU Line Cords The following section expands on the input line cords for North American PDUs for Single-phase and Three-phase options. System x North American PDUs Line Cords The following input line cords are for North American PDUs. NEMA L6-30 NEMA L6-30P (4.3m) 30A (24A Derated) @ 200V-240V Single Phase Compatible with:...
  • Page 86 IEC 309 2P+G – 60A@200-240V 1ph IEC 309 2P+G (4.3m) - 60A (48A Derated) @ 200V-240V Single Phase Plug (Type 360P6W) Only a receptacle or a connector is needed to mate with the plug on the PDU input “IEC 309 Pin & Sleeve Plug Decode" on page 99 line cord.
  • Page 87 NEMA L21-30 Attached 3.0 meter line cord with NEMA L21-30P Plug 30A (13.85A / Phase Derated) @ 200V-240V Three Phase Delta 41.55A Total Derated Circuit Capacity Compatible with: Line Cord PDU + PDU Part Part Line Number / Type Form PDU Name Number Number...
  • Page 88 CS8365L – 50A@208V 3ph Attached 3.0 meter line cord with CS8365L Plug 50A (23.09A / Phase Derated) 200V-240V Three Phase Delta 69.27A Total Derated Circuit Capacity Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord.
  • Page 89 IEC309 3P+G – 60A@208V 3ph Attached 14-foot (4.3 meter) line cord with IEC-309 60A, 3P4W Plug (Type 460P9W) 60A (27.7A / Phase Derated) 200V-240V Three Phase Delta 83.1A Total Derated Circuit Capacity Only a receptacle or a connector is needed to mate with the plug on the PDU input “IEC 309 Pin &...
  • Page 90: System X International Pdus Line Cords

    System x International PDUs Line Cords The following input line cords are for International PDUs (outside of North America). IEC 309 P+N+G – 32A@220-240V 1ph IEC 309 P+N+G (4.3m) - 32A / 220-240V Single Phase Only a receptacle or a connector is needed to mate with the plug on the PDU input “IEC 309 Pin &...
  • Page 91 AUS/NZ 3112 32A – 32A@230V 1ph P+N+G (PDL P/N 56P332) Australia/New Zealand connector Compatible with: PDU + Form PDU Part Line Cord Line Cord Number / Type Facto PDU Name Number Part Number of Outlet Front End Basic 39Y8936 Comes with PDU A11Y 3 / C19 Front ½...
  • Page 92 KSC 8305 30A – 30A@220V 1ph P+N+G (Shin Ju P/N SJ-P3302) Korea connector Compatible with: PDU + PDU Part Line Cord Line Cord Number / Type Form PDU Name Number Part Number of Outlet Factor Comes with Front End Basic 39Y8937 A11X 3 / C19 Front...
  • Page 93 IEC 309 P+N+G – 63A@220-240V 1ph IEC 309 P+N+G (4.3m) - 63A / 220-240V Single Phase Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section “IEC 309 Pin & Sleeve Plug Decode" on page 99 in this document for further details on IEC309.
  • Page 94 IEC309 3P+N+G – 16A@380-415V 3ph IEC-309 3P+N+G 3.0 meter 16A, 3P5W plug (Type 516P6W) 32A (32A / Phase) 380-415V Three Phase Wye 48A Total Circuit Capacity Only a receptacle or a connector is needed to mate with the plug on the PDU input “IEC 309 Pin &...
  • Page 95 IEC 309 3P+N+G – 32A@380-415V 3ph IEC-309 3P+N+G (4.3m) 32A, 3P5W plug (Type 532P6W) 32A (32A / Phase) 380-415V Three Phase Wye 96A Total Circuit Capacity Only a receptacle or a connector is needed to mate with the plug on the PDU input “IEC 309 Pin &...
  • Page 96: Reference Material

    Reference Material What is N+N and N+1 PSU Redundancy N+N PSU redundancy is where N is the minimum number of PSUs needed to keep the system operational, plus N number of PSUs again for redundancy. Essentially, the number of PSUs are double of what is necessary to keep the system operational. N+N is needed when a system needs to be power source redundant (See example diagrams in “Typical PDU Configurations”...
  • Page 97: Iec 320 Connectors

    IEC 320 Connectors...
  • Page 98: Iec 320 Connectors

    IEC 320 Connectors The following table displays the plug types for different hardware such as monitors, switches, servers, high-end servers, power distribution units (PDUs), and uninterpretable power supplies (UPSs). Name Connector Rating Laptop Power Supplies And Other Portable C5 – Female 2.5A Power Supplies C6 –...
  • Page 99: Iec 309 Pin & Sleeve Plug Decode

    IEC 309 Pin & Sleeve Plug Decode...
  • Page 100: Ingress Protection (Ip) Decode

    Ingress Protection (IP) Decode Example: IP67 = Ingress Protection / Dust-Tight / Temporary Immersion 60A Three Phase Delta Power Calculations...
  • Page 101: Three Phase Delta Power Calculations

    50A Three Phase Delta Power Calculations 30A Three Phase Delta Power Calculations...
  • Page 102: Three Phase Delta Power Calculations

    32A Three Phase Delta Power Calculations 16A Three Phase Delta Power Calculations...
  • Page 103: System X6 Documents

    Hubbell - Twist Lock Plug/Outlet Catalog (Includes NEMA Outlets) http://www.hubbellcatalog.com/wiring/catalogpages/section-b.pdf Hubbell - Pin & Sleeve Plug/Outlet Catalog (Includes IEC309 Outlets) http://www.hubbellcatalog.com/wiring/catalogpages/section-E.pdf System x Configuration and Options Guide http://www.ibm.com/systems/xbc/cog/ System x BladeCenter and System x Reference Sheets http://www.redbooks.ibm.com/abstracts/redpxref.html Official System x Visio Stencils http://www.visiocafe.com/ lenovo .ht m...
  • Page 104: Support

    Support...

This manual is also suitable for:

X3950 x6

Table of Contents