Standard mapping 2-1
2.2.1.19 Measurement supervision
Offset
Designation of the
SIPROTEC objects
17/2
Fail I Superv.
17/3
Failure <Sum>I
17/4
Fail Ph. Seq.
17/5
MeasSup OFF
2.2.1.20 Set point alarms
Offset
Designation of the
SIPROTEC objects
17/6
SP. Op Hours>
17/7
SP. IA dmd>
18/0
SP. IB dmd>
18/1
SP. IC dmd>
18/2
SP. I1 dmd>
18/3
SP. |Pdmd|>
18/4
SP. |Qdmd|>
18/5
SP. |Sdmd|>
18/6
SP. 37-1 alarm
18/7
SP. PF(55)alarm
2.2.1.21 Status annunciations
•
Ref. to chap. 1.5.7 for additional notes regarding "Stop data transmission".
Offset
Designation of the
SIPROTEC objects
19/0
>No Volt
19/1
DataStop
19/2
Test mode
19/3
Cntrl Auth (device 7SJ63/6MD63)
19/4
ModeLOCAL (device 7SJ63/6MD63)
19/5
ModeREMOTE
19/6
Cntrl Auth (device 7SJ61/62)
19/7
ModeLOCAL (device 7SJ61/62)
1
Not used in the 7SJ61, 7SJ62.
2
Not used in the 7SJ63, 7SJ65, 6MD63.
2-10
1 = Failure: General current supervision
1 = Failure: Current summation
1 = Failure: Phase sequence
1 = Measurement supervision is switched OFF
1 = Set point operating hours
1 = Set point phase A dmd>
1 = Set point phase B dmd>
1 = Set point phase C dmd>
1 = Set point positive sequence I1 dmd>
1 = Set point |Pdmd|>
1 = Set point |Qdmd|>
1 = Set point |Sdmd|>
1 = Set point 37-1 undercurrent alarm
1 = Set point 55 power factor alarm
1 = Binary input "No voltage (fuse blown)" is active
1 = "Stop data transmssion" is active
1 = Test mode is active
1
Control authority
(0 = REMOTE, 1 = LOCAL)
1
Control mode LOCAL
(0 = LOCKED, 1 = UNLOCKED)
Control mode REMOTE
(0 = LOCKED , 1 = UNLOCKED)
2
Control authority
(0 = REMOTE, 1 = LOCAL)
2
Control mode LOCAL
(0 = LOCKED, 1 = UNLOCKED)
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
Comments
Comments
Comments
C53000-L1840-B006-02
Internal
object no.
161
162
171
197
Internal
object no.
272
273
274
275
276
277
278
279
284
285
Internal
object no.
–
–
–
–
–
–
–
–