1.5.6 Alarm summary event

References

1.5.7 Stop data transmission

References

1.5.8 Fault locator: Fault location

References
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
The "Alarm summary event" is indicated, if at least one of the following
internal alarms assumes the ON status:
"Failure: Current summation", "Failure: Current balance", "Failure:
Voltage balance", "Failure: Phase sequence current", "Failure:
Phase sequence voltage".
Standard mapping 2-1: ref. to chap. 2.2.1.5
Standard mapping 2-2: ref. to chap. 3.2.1.5
Standard mapping 2-3: ref. to chap. 4.2.1.5
Standard mapping 2-4: ref. to chap. 5.2.1.8
The functionality "Stop data transmission" is not supported via
PROFIBUS-DP communication. If "Stop data transmission" is active
nevertheless data via PROFIBUS-DP will be transmitted furthermore.
The annunciation "DataStop" signals the activation of "Stop data
transmission" however and can be evaluated correspondingly in the
PROFIBUS-DP master.
Standard mapping 2-1: ref. to chap. 2.2.1.21
Standard mapping 2-2: ref. to chap. 3.2.1.18
Standard mapping 2-3: ref. to chap. 4.2.1.8
Standard mapping 2-4: not pre-allocated
Always the latest fault location is stored.
In the event of a fault, reading out of the fault record protocol from the
SIPROTEC device is necessary for an exact diagnosis.
Standard mapping 2-1: ref. to chap. 1.5.8
Standard mapping 2-2: not available
Standard mapping 2-3: not available
Standard mapping 2-4: not available
Data in the PROFIBUS-DP messages
1-13