Control/Status Byte; Table 25: Status Byte S0 - WAGO 750-637/040-001 Manual

Incremental encoder interface; 24 vdc; differential input; 32 bits; extreme for wago-i/o-system 750 xtr
Table of Contents

Advertisement

32
Process Image
4.1

Control/Status Byte

Table 25: Status Byte S0

Bit 7
0
LATC_VAL
LAT_EXT_VAL
CNT-SET_ACK
UNDERFLOW
OVERFLOW
AckSet LoadExt
X
0
Manual
Version 1.1.0
750-637/040-001 Inc. Encoder 24 VDC Diff 32Bit XTR
Status Byte S0
Bit 6
Bit 5
Bit 4
X
AckSet
OVER-
LoadExt
FLOW
Ack Bit for EN-LATC (C0.0)
This bit is set on a positive edge at input C
Latch Mode:
Reset is carried out when EN_LATC is reset
This bit is set on a positive edge at input C
Preload Mode:
Reset is carried out when EN_LATC is reset
Ack Bit for EN-LAT_EXT (C0.1)
This bit is set on a positive edge at the Latch input
Latch Mode:
Reset is carried out when EN_LAT_EXT is reset
This bit is set on a positive edge at the Latch input
Preload Mode:
Reset is carried out when EN_LAT_EXT is reset
Ack Bit for CNT_SET (C0.2)
Reset is carried out when CNT_SET=0.
UNDERFLOW
1:
On counter underflow from 0x00000000 to 0xffffffff
When counter value < 0xAAAAAAAA
0:
With a positive edge for ResetUnderflow (C0.3)
When OVERFLOW=1
OVERFLOW
1:
On counter overflow from 0xffffffff to 0x00000000
When counter value < 0x55555555
0:
With a positive edge for ResetOverflow (C0.4)
When UNDERFLOW=1
Ack Bit for SetLoadExt
Reset is carried out when SetLoadExt=0 (C0.5)
Reserved
Reserved
WAGO-I/O-SYSTEM 750 XTR
Bit 3
Bit 2
UNDER-
CNT-SET_
FLOW
ACK
Bit 1
Bit 0
LAT_
LATC_
EXT_
VAL
VAL

Advertisement

Table of Contents
loading

This manual is also suitable for:

Inc. encoder 24 vdc diff 32bit xtr

Table of Contents