Commissioning

6
Commissioning
6.1

Configuration of switching outputs

The switching points are set at the factory to the angular positions 30° (S1) and 220° (S2). Con-
figuration can be used to locate these switching points at each desired position. To configure
switching output 1 (S1), proceed as follows:
Configuration of S1 switching output
1.
Make sure that the sensor is correctly and securely mounted and that a target with the specified
dimensions is located at the correct distance to the sensor surface (see chapter entitled
Installation).
The sensor's green LED lights up.
2.
Move the target to the desired position at which the S1 switching output is to be active.
3.
Press the S1 button for  2 s.
The yellow LED flashes to indicate the teach-in position of the S1 switching point.
4.
Check that the target is in the correct position and press the S1 button again.
The setting is now saved in the sensor's memory. The yellow S1 LED now lights up perma-
nently. This serves to indicate that the S1 switching point has been successfully taught at
the current position.
To configure switching output 2 (S2), proceed in the same way. Actuate the S2 button for this
purpose. An indication is made by the S2 LED.