The iKAN display device provides Modbus registers for 40 coil variables, allowing the Host PC or a
PLC to read or write data via the Modbus TCP/ RTU protocol. These values can also be inserted
into a message. If these values are modified via a remote Host or a PLC, the value will be
automatically refreshed when it is displayed on the iKAN series device.
The format for using a variable in a message is a 5-byte string, as follows:
1
Delimiter Character
%
A maximum of 40 Coil type variables can be stored on the iKAN series device, and are accessed
using Modbus register addresses 00000 to 00039.
Modbus Address
Decimal
Hex.
00000
0000
:
:
00039
0027
00100
0064
:
:
00227
00E3
iKAN Series Display User Manual
2
Variable Type
b: Coil
Length
40
Coil-type variables
Enables or disables the display of
128
Common Messages 0 to 127.
Modbus Address: 3-digit decimal number
X
Description
v 1.0.1
3 to 5
X
X
Value
Attribute
Range
-
R/W
0: Disabled
R/W
1: Enabled
Page: 84