Inserting Integer-Type Variables Into A Message - ICP DAS USA iKAN Series User Manual

Hide thumbs Also See for iKAN Series:
Table of Contents

Advertisement

4.2.2. Inserting Integer-type Variables into a Message

iKAN display devices provide Modbus registers for 64 integer variables, allowing the Host PC or a
PLC to read or write data via the Modbus TCP/ RTU protocol. These values can also be inserted
into a message. If these inserted values are modified via a remote Host or a PLC, the value will be
automatically refreshed when it is displayed on the iKAN series device.
The format for using a variable in a message is a 5-byte string as follows:
1
Delimiter
Variable Type
Character
u: Unsigned integer (0 to 65535)
%
i: Signed integer (-32768 to 32767)
A maximum of 64 integer variables can be stored on the iKAN series device, and are accessed
using Modbus register addresses 40000 to 40063.
Modbus Address
Decimal
Hex.
40000
0000
:
:
40063
003F
iKAN Series Display User Manual
2
Length
Description
64
Integer-type variables
3 to 5
Modbus Address:
3-digit decimal number
X
X
Value Range
0 to 65535
v 1.0.1
Page: 78
X
Attribute
R/W

Advertisement

Table of Contents
loading

Table of Contents