Explanation Of Parameters - Siemens SIMATIC ET 200SP Manual

Digital module dq 8x24vdc/0.5a hf
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

4.2

Explanation of parameters

Diagnostics: No supply voltage L+
Enabling of the diagnostics for no or insufficient supply voltage L+.
Diagnostics: Short-circuit to ground
Enabling of the diagnostics if a short-circuit of the actuator supply to ground occurs.
Diagnostics: Short-circuit to L+
Enabling of the diagnostics if a short-circuit of the actuator supply to L+ occurs.
Diagnostics: Wire break
Enabling of the diagnostics if the line to the actuator is broken.
Channel activated
Determines whether a channel is activated or deactivated.
Reaction to CPU STOP
Determines the behavior of the module in the event of a CPU STOP.
Potential group
A potential group consists of a group of directly adjacent I/O modules within an ET 200SP
station, which are supplied via a common supply voltage.
A potential group begins with a light-colored BaseUnit through which the required voltage is
supplied for all modules of the potential group. The light-colored BaseUnit interrupts the
three self-assembling voltage buses P1, P2 and AUX to the left neighbor.
All additional I/O modules of this potential group are plugged into dark-colored BaseUnits.
You take the potential of the self-assembling voltage buses P1, P2 and AUX from the left
neighbor.
A potential group ends with the dark-colored BaseUnit, which follows a light-colored
BaseUnit or server module in the station configuration.
See also
See system manual ET 200SP distributed I/O system
(http://support.automation.siemens.com/WW/view/en/58649293).
Digital output module DQ 8x24VDC/0.5A HF (6ES7132-6BF00-0CA0)
Manual, 12/2017, A5E03576680-AE
Parameters/address space
4.2 Explanation of parameters
19

Advertisement

Table of Contents
loading

Table of Contents