Interrupts/diagnostics alarms
5.1 Status and error displays
Meaning of the LEDs
The tables below explain the meaning of the status and error displays. Corrective measures
for diagnostics alarms can be found in section Diagnostics alarms (Page 30).
DIAG LED
Table 5- 1
DIAG LED
LED channel status/channel error
Table 5- 2
LED channel
PWR LED
Table 5- 3
PWR LED
28
Error display of the DIAG LED
Meaning
Backplane bus supply of the ET 200SP not OK
Off

Module not ready for operation (no parameters assigned)
Flashes
Module parameters assigned and no module/channel diagnostics
On
Module parameters assigned and module/channel diagnostics
Flashes
Status / error display of the LED channel status / channel error
LED channel
status
error
Off

Off

On
Off

Off

On
Status display of the PWR LED
Meaning
Missing supply voltage L+
Off

Supply voltage L+ present
On
Meaning
Channel deactivated or process signal = 0
and no channel diagnostics
Channel activated and process signal = 1
and no channel diagnostics
Channel activated and channel diagnostics
Digital output module DQ 8x24VDC/0.5A HF (6ES7132-6BF00-0CA0)