Siemens SIMATIC ET 200SP Manual page 19

Digital module dq 8x24vdc/0.5a hf
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameters/address space
4.1 Parameters
Parameter
Reaction to CPU STOP •
Potential group
Due to the limited number of parameters of a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD
1
configuration, the parameter assignment options are restricted. The parameter length of the I/O module is 7 bytes with
PROFIBUS GSD configuration. If necessary, you can set this parameter, however, with data records 64 to 71 or data
record 128, see Appendix "Parameter data record".
Note
If one of the two parameters "Diagnostics: Short-circuit to L+" or "Diagnostics: Wire break" is
enabled and one of these diagnostics occurs, the affected channel is switched off to avoid
triggering an undefined load. Note that a diagnostic interrupt can only be generated when
diagnostics are enabled. *
as of module revision 05
*
18
Value range
Turn off
Turn off
Keep last value
Output substi-
tute value 1
Use potential
Use potential
group of the left
group of the left
module
module (module
plugged into a
dark-colored
BaseUnit)
Enable new
potential group
(module plugged
into light-colored
BaseUnit)
Default
Configuration
in RUN
Yes
No
Digital output module DQ 8x24VDC/0.5A HF (6ES7132-6BF00-0CA0)
Scope with configuration software,
e.g., STEP 7 (TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Channel
Module
Module
Module
Manual, 12/2017, A5E03576680-AE