Technical specifications
6.1 Technical specifications
Article number
Potential separation
Potential separation channels
between the channels
•
between the channels and backplane bus
•
Isolation
Isolation tested with
Dimensions
Width
Height
Depth
Weights
Weight, approx.
Safety-related shutdown
Note
The digital output module DQ 8x24VDC/0.5A HF supports safety-related shutdown in
connection with a fail-safe power module F-PM-E 24VDC/8A PPM ST:
• SIL according to IEC 61508: 2
• Highest attainable safety class in safety mode, performance level according to EN ISO
13849-1: d
Residual current for signal state "0"
Note
Residual current for signal state "0"
Due to the Diagnostics: Wire break function, there is a low level of residual current in the "0"
signal state at the output, which may cause the display diodes to flicker.
This residual current does not depend on the setting for the Diagnostics: Wire break
parameter.
Dimension drawing
See manual ET 200SP BaseUnits
(http://support.automation.siemens.com/WW/view/en/58532597/133300)
34
6ES7132-6BF00-0CA0
No
Yes
707 V DC (type test)
15 mm
73 mm
58 mm
30 g
Digital output module DQ 8x24VDC/0.5A HF (6ES7132-6BF00-0CA0)
Manual, 12/2017, A5E03576680-AE