Connection to central heating radiators with another boiler support and
sanitary water combined with solar panel
1
Figura 64 – Connection to central heating radiators with another boiler support and sanitary
water combined with solar panel
Note:
- The chrono-thermostat Earth leakage must have a hysterisis of 15 to 25 ° C.
1
- Hydro independiente "Off" (water temperature controlled regulation), put the boiler
in "manual" mode and power nivle to "5"
- Modulating pump "On"
- Water sensing inhibition "On"
- Alternative hydro shutdown "On"
- Pump "On" = 50 ° C
- Pump "Off" = same or thermostat temperature 1 ° C below the temperature
differential thermostat
When using the generator with differential thermostat the machine must be
connected in the CONNECTION "Remote".
Calculation deposits of inertia: the boilers for pellets is recommended that the buffer
tank has 20l/kW.