Boiler Startup - Baxi CBP Matic 18 Manual

Pellet boiler
Table of Contents

Advertisement

Available languages

Available languages

Within this menu, you should enter the General Settings, and in the Pellet Level
Sensor menu you should press Set, and then the keys "+" and "-" until it shows On on
the display.
When the storage unit runs out of pellets, the level sensor sends a signal and an
alarm appears in the boiler's display (A15 code). You should refill the storage unit
with pellets, reset the alarm and restart the boiler.

Boiler startup

With the storage unit properly fixed to the boiler (right or left side) you should carry
out the hydraulic connections and the connection of the boiler to the fumes outlet.
After making the connections, you should introduce some pellets inside the storage
unit and start the operation of the boiler. You must observe the pellets falling from the
storage unit to the boiler's internal tank and check if the level sensors work properly.
If the sensors do not work properly, you should remove them and re--adjust
the sensitivity.
You must observe the boiler working for a time period corresponding to 3 or 4
charges of pellets and check if the pellet level does not rises above the level of the
sensors.