SECTION 7 – BOILER SEQUENCING TECHNOLOGY
OPTION 3 Instructions: Outdoor Reset, Direct Wired Header Temp Sensor & Outdoor Sensor
Step 3 – OPTION 3 CONFIGURATION
On All Boiler:
Main Menu → Advanced Setup → BST Cascade → Cascade
1. Go to:
•
Set the Unit Mode parameter to BST Client.
Main Menu → Advanced Setup → BST Cascade → Application
2. Go to:
•
Set the Unit Address parameter to the communication address of the unit.
On the BST Manager only:
Main Menu → Advanced Setup → BST
1. Go to
in each menu in the table below.
Menu/Screen Name
Cascade
Configuration
Application
Configuration
Cascade Comm
OMM-0145_A99 • GF-218 •
Parameters
Auto Manager
Transfer
Unit Mode
Hdr Temp Sensor
Application
SH Operating Mode
Outdoor Temp Sensor
Plant Setpoint
Min address
Max address
Cascade Baud Rate
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
9/18/2019
Cascade, set the Parameters to the Values
Values
Disabled (This option is available on the
Manager unit only)
BST Manager
FFWD Temp
Space Heating
Outdoor Reset
Direct
Header temperature required for the cascade
The minimum unit address in the cascade
The maximum unit address in the cascade
The baud rate for the cascade.
Configuration:
Configuration:
Page 112 of 157