Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 7 – BOILER SEQUENCING TECHNOLOGY

Option 2 Constant Setpoint: Modbus Wired Header Temp Sensor

7.3.2
OPTION 2 Instructions: Constant Setpoint with Modbus Wired Header Temp Sensor
Step 1: MODBUS HEADER TEMP SENSOR WIRING – ANY BOILER
Using the Modbus Transmitter provides gives the plant the ability to use the Backup
manager feature. This allows the any of the client units to become a Backup manager if
the manager unit is not communicating.
1. Connect the Modbus Transmitter terminal Pin B to the RS485+ terminal, and Pin A to
the RS485- terminal on the I/O Board of any Boiler unit, using shielded pair 18 - 22 AWG
cable.
2. Connect the Header Temp Sensor to pins 2 and 3 of the Modbus Transmitter using
shielded pair 18 - 22 AWG cable.
3. Install a jumper wire between pins 1 and 2 of the Modbus Transmitter.
NOTES:
Polarity must be observed for the RS485 connections.
Ground the shield to any SHLD terminal on the I/O Board.
The Header Temp Sensor must be installed between 2 and 10 feet (0.61 and 3.1m)
downstream of the last boiler in the plant's supply water header.
There is no polarity to be observed. The ground for the shield is at the power supply
ground. The sensor end of the shield must be left free and ungrounded.
HEADER TEMP SENSOR
Step 2: OPTION 2 CONFIGURATION
On All Boiler:
Main Menu → Advanced Setup → BST Cascade → Cascade
1. Go to:
Set the Unit Mode parameter to BST Client.
Main Menu → Advanced Setup → BST Cascade → Application
2. Go to:
Set the Unit Address parameter to the communication address of the unit.
OMM-0145_A99 • GF-218 •
MODBUS TRANSMITTER
Continued on next page
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
9/18/2019
I/O BOARD
Configuration:
Configuration: