Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 6 – MODES OF OPERATION
Combination Control System Setup Instructions
1.
As a prerequisite, verify that the unit is not a BST Client or Manager. Go to:
→ Advanced Setup → BST Cascade → Cascade
2. On the Controller, go to:
Configuration.
3. Press SH Operating Mode and choose Combination.
4. Press the Remote Signal parameter and choose Network.
While it is possible to change other temperature-related functions for Combination mode, these
functions are preset at the factory. These default settings work well in most applications. It is
suggested that AERCO be contacted prior to changing settings other than the unit's setpoint.
OMM-0145_A99 • GF-218 •
Main Menu → Advanced Setup → Unit →Application
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
9/18/2019
Configuration, Unit Mode = Off.
Main Menu