Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 5 – SAFETY DEVICE TESTING
HIGH Gas Pressure Test Instructions: BMK3000 – 6000 ONLY
NATURAL GAS HIGH GAS
PRESSURE SWITCH
- BMK6000 – 10.5" W.C., 2.6 kPa
- BMK5000 – 11.0" W.C., 2.7 kPa
NATURAL GAS HIGH Gas
Pressure Port
Install manometer here for High
Gas Pressure test
PROPANE Gas Pressure Port
Install manometer here for High Gas Pressure test
Alternative location for manometer
if hose barb is preferred
Figure 5-4c: High Gas Pressure Switch Locations & Test Ports – BMK6000
OMM-0145_A99 • GF-218 •
Shown
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
9/18/2019
DOWNSTREAM
SSOV WITH POC
SWITCH
PROPANE HIGH GAS
PRESSURE SWITCH
- BMK6000 – 10.5" W.C., 2.6 kPa
- BMK5000 – 4.5" W.C., 1.1 kPa
Page 83 of 157