Benchmark6000 Air/Fuel Valve Position And Energy Input - Watts AERCO Benchmark BMK750 Operation And Service Manual

With edge (i) controller
Hide thumbs Also See for AERCO Benchmark BMK750:
Table of Contents

Advertisement

Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 3 - START SEQUENCE

Benchmark6000 Air/Fuel Valve Position and Energy Input

3.4.8
BMK6000 Air/Fuel Valve Position and Energy Input
Air Fuel Valve
Position
(% Full Open)
10%
18% (Stop Level)
20%
30%
40%
50%
60%
70%
80%
90%
BMK6000 Gas Pressure De-Rating Chart
Gas Pressure @ SSOV
in inches W.C. (kPa)
Inlet
56"
(13.9 kPa)
14"
(3.49 kPa)
13"
(3.23 kPa)
OMM-0145_A99 • GF-218 •
Boiler Energy Input
BTU/Hr
0
385,000
(113 kW)
400,000
(117 kW)
540,000
(158 kW)
770,000
(226 kW)
1,160,000 (340 kW)
1,650,000 (484 kW)
2,386,000 (699 kW)
3,515,000 (1030 kW)
4,650,000 (1362 kW)
Energy Input in
Outlet
8"
(1.99 kPa)
6,000,000 (1758 kW)
8"
(1.99 kPa)
6,000,000 (1758 kW)
8"
(1.99 kPa)
5,860,000 (1717 kW)
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
9/18/2019
% of Full
Capacity
0%
6%
7%
9%
13%
19%
28%
40%
59%
78%
Oxygen
BTU/hr
(%O
2
5.40
5.40
5.45
De-rating
)
(% Full Fire)
0%
0%
2%
Page 47 of 157

Advertisement

Table of Contents
loading

Table of Contents