Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 2: OPERATION
Lag Unit
Main Menu
2.3.4.3
Main Menu → Advanced Setup → Comm & Network → onAER
onAER Mode
Unit Upload Time
Cascade Upload Time
Status
Main Menu → Advanced Setup → Comm & Network → Ethernet
DHCP
IP Address
Subnet
Gateway
DNS1
DNS2
ICMP PING
Main Menu → Advanced Setup → Comm & Network → Communication Failsafe
Unit Failsafe Mode
Unit Failsafe Setpoint
Main Menu
2.3.4.4
Main Menu → Advanced Setup → Ancillary Device → Interlocks
Remote Interlock Name
Remote Interlock Use
Delayed Interlock Name
Auxiliary Delay
Main Menu
2.3.4.5
Main Menu → Advanced Setup → Performance → Temperature Control
Main Menu → Advanced Setup → Performance → Temperature Control → PID Setting
Proportional Band
Integral Band
OMM-0145_A99 • GF-218 •
Numeric Entry
Advanced Setup
Select
Numeric Entry
Numeric Entry
Read Only
Enable/Disable
Numeric Entry
Numeric Entry
Numeric Entry
Numeric Entry
Numeric Entry
Enable/Disable
Toggle
Numeric Entry
Advanced Setup
Select
Toggle
Select
Numeric Entry
Advanced Setup
Numeric Entry
Numeric Entry
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
9/18/2019
Specify the address of the Lag unit (0 to 16, Lead/Lag Setting
= Select Lead Lag).
Com & Failsafe
To enable onAER, select the communication method:
Ethernet, Wi-Fi or Wiznet (for units where the Edge
Controller replaced a C-More).
Determines how frequently unit data is uploaded to the
server (30 to 9999 sec.).
Determines how cascade data is uploaded to the server
(60 to 9999 sec.).
The communication interface status.
Enables/disables
DHCP (Dynamic Host Configuration
Protocol).
The static IP address of the unit (DHCP = Disabled).
The subnet address of the network (DHCP = Disabled).
The IP address of the Gateway (DHCP = Disabled).
The IP address of DNS Server 1 (DHCP = Disabled).
The IP address of DNS Server 2 (DHCP = Disabled).
Allows the unit to be pinged..
Choose how the unit will operate when either the Manager
communication or a Remote Signal is lost: Constant Setpt
or Shutdown.
The unit's default setpoint when communication fails (60 to
160°F, Unit Failsafe Mode = Constant Setpt).
Ancillary Devices
Choose the Remote Interlock: Flow, Damper, Louver,
Other.
Specify what will shut down if the selected Remote
Interlock is open: Unit Shutdown or Sys Shutdown.
Choose the Delayed Interlock: Valve 1, Valve 2, Louver 1
or Louver 2.
Select the Delayed Interlock's delay (0 to 240 sec.).
Performance
Generates a fire rate based on the error that exists
between the setpoint and the actual outlet temperature. If
the error is less than Proportional Band, fire rate will be
less than 100%. If the error is equal to or greater than
proportional band, the fire rate will = 100% (1°F to 120°F).
Specifies the fraction of the output, due to setpoint error, to
add or subtract from the output each minute to move
towards the setpoint. (0.00 to 5.00)
Page 26 of 157