List of Related Parameters

The following tables list the parameters which are required to be set.
To make communications between an inverters and a connected device, set the inverter parameters to match the
communication specifications of the connected device. Data communications cannot be made if the settings are not made or
if there is any setting error.
Required parameter settings
Parameter
Name
Pr.77
Parameter write selection
Pr.544
CC-Link extended setting
Pr.1424
Ethernet communication
network number
Pr.1425
Ethernet communication
station number
Pr.1427
Ethernet function selection 1
Pr.1428
Ethernet function selection 2
Pr.1429
Ethernet function selection 3
Pr.1430
Ethernet function selection 4
Pr.1434
Ethernet IP address 1
Pr.1435
Ethernet IP address 2
Pr.1436
Ethernet IP address 3
Pr.1437
Ethernet IP address 4
Pr.1438
Subnet mask 1
Pr.1439
Subnet mask 2
Pr.1440
Subnet mask 3
Pr.1441
Subnet mask 4
Pr.1449
Ethernet command source
selection IP address 1
Pr.1450
Ethernet command source
selection IP address 2
Pr.1451
Ethernet command source
selection IP address 3
Pr.1452
Ethernet command source
selection IP address 4
Parameter settings (for adjustment and operation)
Parameter
Name
Pr.1432
Ethernet communication
check time interval
For the FR-A800-E/F800-E parameters, refer to the following.
Page 55 Parameters
2 INVERTER SETTINGS
9
2.2 List of Related Parameters
Initial
Setting value
value
(Inverter station
number 1)
0
2
0
18
1
1
1
1
5001
5001
45237
45237
45238
61450
9999
9999
192
192
168
168
50
50
1
11
255
255
255
255
255
255
0
0
0
192
0
168
0
50
0
2
Initial value
Setting value
(Common for both
inverters)
1.5 (= 1.5 seconds)
5.0 (= 5 seconds)
Setting value
Description
(Inverter station
number 2)
Parameter write is set to [enable].
Set the function of the remote register for the CC-Link IE
Field Network Basic to [Compatible with the octuple
setting of CC-Link Ver.2].
Set this parameter when making communications
between the inverters and FR Configurator2.
Set a network number to Pr.1424 and a station number
2
to Pr.1425.
Set this parameter when making communications
between the inverters and FR Configurator2.
In this manual, use Pr.1427 and Pr.1428 with the initial
values.
Change the settings of the application to [CC-Link IE
Field Network Basic].
Use this parameter with the initial value.
Set an IP address of the inverter to be connected to
Ethernet.
12
Set a subnet mask which the IP address of the inverter
belongs to.
Set an IP address of the FX5U CPU module.
Description
Set "9999" during adjustment, and set a value in accordance
with the system specification during operation.
• 9999: No communication check (signal loss detection)
• 0: Ethernet communication is available, but the inverter
output is shut off in the NET operation mode.
• 1 to 9998: Set the interval of the communication check
(signal loss detection) time for all devices with IP addresses
in the range specified for Ethernet command source
selection (Pr.1449 to Pr.1454).