Chapter 4 Coummunication Check Over Cc-Link Ie Field Network Basic - Mitsubishi Electric MELSEC iQ-F Series Quick Connection Manual

For cc-link ie field network basic
Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

4
COUMMUNICATION CHECK OVER CC-Link IE
Field Network Basic
This chapter describes how to check communications over CC-Link IE Field Network Basic in the system where the inverters
and the programmable controller are connected.
1.
On GX Works3, select [Online] on the toolbar  [Monitor]  [Device/Buffer Memory Batch Monitor].
2.
Enter "X100" in "Device Name", and click the [Start Monitoring] button. To make sure that the inverters and the
programmable controller are communicating properly, check X133 of the station number 1 and X233 of the station
number 2 which are the "Remote station ready" signals of these stations.
Normal communications
X133 of the station number 1 and X233 of the station number 2 are ON (set to "1" on the monitor window).
Faulty communications
X133 of the station number 1 and X233 of the station number 2 are OFF (set to "0" on the monitor window). Check the error
status.
For how to check the error status, refer to the following.
Page 43 TROUBLESHOOTING
FX5U CPU module
Ethernet
X133
X233
4 COUMMUNICATION CHECK OVER CC-Link IE Field Network Basic
FR-E800-E
Hub
FR-E800-E
4