4
COUMMUNICATION CHECK OVER CC-Link IE
Field Network Basic
This chapter describes how to check communications over CC-Link IE Field Network Basic in the system where the inverters
and the programmable controller are connected.
1.
On GX Works3, select [Online] on the toolbar [Monitor] [Device/Buffer Memory Batch Monitor].
2.
Enter "X100" in "Device Name", and click the [Start Monitoring] button. To make sure that the inverters and the
programmable controller are communicating properly, check X133 of the station number 1 and X233 of the station
number 2 which are the "Remote station ready" signals of these stations.
Normal communications
X133 of the station number 1 and X233 of the station number 2 are ON (set to "1" on the monitor window).
Faulty communications
X133 of the station number 1 and X233 of the station number 2 are OFF (set to "0" on the monitor window). Check the error
status.
For how to check the error status, refer to the following.
Page 43 TROUBLESHOOTING
FX5U CPU module
Ethernet
X133
X233
4 COUMMUNICATION CHECK OVER CC-Link IE Field Network Basic
FR-E800-E
Hub
FR-E800-E
4
32