SmartLi 2.0
User Manual
Alarm ID
Alarm
(Alarm ID-
Name
Cause ID)
0630-3
Abnormal
intra-battery
cabinet
parallel
cable
0620-9
BCU fault
0631-2
Version
incompatible
0631-3
Version
incompatible
0631-4
Version
incompatible
0631-1
Version
incompatible
0632-1
Lithium
battery
system
communicati
on failure
0174-2
Software
package not
exist
0246-2
Cabinet
quantity
mismatch
Issue 03 (2020-08-07)
Severi
Cause
ty
Critica
The BCU is not
l
properly
connected to the
signal transfer
board.
Critica
The intra-rack
l
parallel cable is
faulty.
Critica
The DSP software
l
version of the BCU
does not match.
Critica
The FPGA
l
software version
of the BCU does
not match.
Critica
The battery
l
module software
is incompatible.
Critica
The software
l
version of the BCU
does not match.
Minor
The
communication
between the UPS
monitoring unit
and the lithium
battery is
interrupted.
Critica
The package of
l
the power unit or
module does not
exist in the
monitoring
system.
Minor
The configured
number of battery
cabinets does not
match the actual
available number.
Copyright © Huawei Technologies Co., Ltd.
Solution
1. Check that the cable between the
BCU and the signal transfer board
is properly connected.
2. Replace the BCU or signal transfer
board.
Replace the BCU.
Load the software.
Load the software.
Load the software.
Load the software.
Check the cable between the UPS
monitoring unit and the lithium
battery.
Upload the software packages of the
power unit or module and MDU, and
activate all the packages.
1. Set the number of battery cabinets
to be the same as the actual
number.
2. Check the parallel cable
connection.