Communication
Data rate
EDS file
Topology
Installation
Max. Stations
Isolation
Response speed
Communication
Data rate
EDS file
DLR (Device Level Ring) Available
TCP/IP settings
Topology
Installation
Web client
Isolation
Response speed
Communication
Data rate
ESI file
Topology
Installation
Isolation
Response speed
Communication
Data rate
Topology
Installation
Max. Stations
Isolation
Response speed
BX11 Smart Process Indicator, User Manual, Rev. 1.8, May 2017
BX11 CO CANopen
10 kbit/s – 1 Mbit/s (selectable) kbit/s
Generic EDS-file provided
Line with Trunkline, Dropline structure and Termination at both Ends
Line length depending on baudrate 25 – 500 meter.
2 wires shielded twisted pair cable.
Alternatively 4 wire with 24 Volt power over the bus
Up to 127 stations per network
Galvanically isolated bus electronics
Up to 4 ms. response delay after read/write commands
BX11 EI EtherNet/IP
10 Mbit/s or 100 Mbit/s, full duplex
Generic EDS-file provided
DHCP or manual IP assign over EtherX PC Software.
Device identity customization
Line, Bus, Star or Tree topology depending on physical media
Switched Ethernet transmission with shielded twisted pair cables and RJ-45
connectors.
Available
Galvanically isolated bus electronics
Up to 4 ms. response delay after read/write commands.
BX11 EC EtherCAT
100 Mbit/s, full duplex
Generic ESI-file provided
Line, Tree, Star or Daisy-chain topology depending on physical media
Switched Ethernet transmission with shielded twisted pair cables and RJ-45
connectors.
Galvanically isolated bus electronics
Up to 4 ms. response delay after read/write commands.
BX11 CC CC-Link
156 kbit/s – 10 Mbit/s (selectable)
Line with Trunkline, Branch structure and Termination at both Ends.
3 wires shielded twisted pair cable.
Up to 64 stations per network
Galvanically isolated bus electronics
Up to 4 ms. response delay after read/write commands
Page 40 of 48