Window Output:
2 set point values are entered. The output
is active when the weight is between
SP1_L and SP1_H. Inverse function is
available. Refer to parameter [ 7-- ] on
Page 30.
PLC remote port
The digital output is used as a remote port
of the PLC if the output is programmed as
fieldbus port.
The PLC sends the command to set the
status of the digital output. The output
status is latched in the weighing
instrument until receiving the following
command as shown in the drawing.
Refer to parameter [ 130 ] and [ 7-- ] on
Page 30.
RS 232C Connection
RS 232C port usage and specifications are shown in the table below.
Interfacing with PC or PLC, remote display connection,
Usage
programming via IndFace1X
Continuous, Fast Continuous, Printer Format, BSI Protocol,
Data
formats
Modbus-RTU High-Low, Modbus-RTU Low-High
1200 / 2400 / 4800 / 9600 (Default) / 19200 / 38400 / 57600 / 115200 bps
Baud rate
8 bit no parity (Default), 7 bit odd, 7 bit even, 8 bit odd, 8 bit even
Length
and parity
Start/
1 start bit and 1 stop bit
Stop bits
BX11 Smart Process Indicator, User Manual, Rev. 1.8, May 2017
(Parameter [ 000 ])
(Parameter [ 001 ])
(Parameter [ 004 ])
Page 19 of 48